GE Industrial Solutions Spectra Series Power Panelboards AMCB6EB, AMCB4SE, AMCB4EB User Manual

Spectra series™ power panelboards, Application, Installation

Advertising
background image

g

Spectra Series™ Power Panelboards

Bolt-On Circuit Breaker Kits
Catalog Numbers AMCB6EB, AMCB4SE, AMCB4EB

Application

For use with circuit breaker types TEB, TED, THED, SED,
SEH, SEL, SEP.
For Use with Circuit Breaker Cover Kit Catalog Numbers
AFP3SED, AFP4SED, AFP2TED, AFP3TED.

Installation

WARNING: Danger of electrical shock or injury.
Turn

OFF power ahead of the panelboard or

switchboard before working inside the equipment or
removing any component

.

Equipment is to be

installed and maintained by properly trained and
qualified personnel only.

In the following instructions and figures, numbers in brackets
refer to the items in Table 1.
For Spectra APNB bolt-on–style interiors, locate the side of the
panel interior for which the dimension from the nearest vertical
bus face to the inner face of the bus support rail is 2.75 inches,
as indicated in Figure 2. The circuit breaker straps will be
mounted on this side of the bus.

1. Install Circuit Breaker Straps. Install the straps beginning

with the outermost (A and C) poles, as shown in Figure 1.
Align the straps [1, 2] back to back, as shown. Slide the
square hole in the antiturn clip [12] over the corresponding
square shank of the carriage bolt [3], then insert the pin
section of the clip through the circular hole in the strap
assembly, with the carriage bolt extending through the
square hole immediately below. Fasten the complete strap
assembly loosely to the vertical bus, using a Belleville
washer [4] and nut [5]. Repeat the procedure for the
opposite pole, leaving 1.38 inches (1X) of space for the
center pole (see Table 2 for one- and two-pole connection
combinations). Align the center-pole straps [6] as shown
and fasten them loosely to the vertical bus using the same
clip, bolt, washer, and nut assembly.

2. Install Circuit Breaker Mounting Straps and Cover

Supports. Fasten the circuit breaker mounting brackets [7]
to the panel side rails using the thread-forming screws [8]
provided, as shown in Figure 1. Tighten the thread-
forming screws to 25 inch-pounds. Using the uppermost slot
on each cover support body, slide the cover supports
(included in the circuit breaker cover kit), with their
mounting tabs oriented inward, onto each bracket until
they snap into place. The cover supports can be easily
removed by inserting a screwdriver into the mounting slot
on the underside of the mounting bracket assembly and
gently prying downward while pushing off the cover
support.

3. Install Circuit Breakers. Position the circuit breakers such

that the line- or ON-side terminals rest on the straps and
the opposite sides are supported by the mounting brackets.
Align the holes in each circuit breaker body with the
corresponding holes in the mounting bracket. Fasten the
breakers to the brackets with the sheet-metal screws [10]
and cup washers [11] and tighten to 20 inch-pounds. Join
the line-side circuit breaker terminals to the threaded holes
in the straps using the screws [9] provided. Tighten the
line-side screws to 32 inch-pounds. Note that the straps
may require minor adjustments for proper hole alignment.

4. Tighten Bolted Connections. Tighten the bolted strap

connections at the vertical bus to 65 inch-pounds. It may be
necessary to remove the adjacent circuit breakers to allow
access to the bolted connections at the vertical bus.

Item Description

Qty.

1

A & C pole outer straps

2

2

A & C pole inner straps

2

3

1

/

4

-20 x 1.50" carriage bolts

3

4

1

/

4

" Belleville washers

3

5

1

/

4

-20 hex nuts

3

6

B-pole straps

2

7

Breaker mounting brackets *

2

8

Thread-forming screws

4

9

Screws with lockwashers

6

10

8-32 x 2

3

/

4

" screws

4

11

#8 cup washers

4

12

Antiturn clips

3

* Kit AMCB4EB uses an alternate 2X mounting bracket.

Table 1. Bolt-on circuit breaker assembly parts, replacement hardware