GE Industrial Solutions EntelliGuard G Back Connected Terminations for Cassette Envelope 1 & 2 (Up to 1600A) User Manual

Entelliguard

Advertising
background image

Back Connected Terminations
Cassette Envelope 1 & 2 (Up to 1600A)

Terminal assemblies are supplied with the
Entelliguard breaker.






































Back Connected Terminations Assembly Procedure:


1. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the

breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
cassette before continuing.


2. Assemble the top and bottom rear vertical

terminal assemblies to the cassette back terminal
support as shown in Fig A.

3. Terminal assemblies to be tightened with M6

hardware as shown in fig A, to 10 Nm (7.38 ft-lbs)
torque.

4. Assemble the remaining rear terminal assemblies

similarly on all the poles to populate 3 pole / 4
pole breaker fig B & C.

5. The bus bars to be supported within 200mm

distance and tightened to 50Nm (36.9 ft-lbs)
torque.

Envelope Size Catalog #

TYPE

GBB216TBBC3 3 pole

Envelope 1

GBB216TBBC4 4 pole
GBB216TBBC3 3 pole

Envelope 2

GBB216TBBC4 4 pole

EntelliGuard

®

G

Circuit Breaker

Accessories

Back Connected Terminations for
Cassette

WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation, et décharger les

resorts d’armement

DEH-41430 Installation Instructions

Terminal

Asm

M6 Hardware

10 Nm torque

M6

Washer

Terminal

Asm

M6 Hardware

10 Nm torque

M6

Washer

Fig A. Back Connected Termination assembly up

to 1600 Amperes (ANSI / UL)

Table 1: Back Connected Terminations

Catalog numbers