7. Install the disconnect handle.
Mount the disconnect
handle as shown in Figure 11. The base of the handle
must be oriented so that the
OFF
indicator is on top
and the
ON
indicator is on the right. The handle
must be pointing down. Cover selection ([3], [4], or
[5]) is dependent on the width of the panelboard or
switchboard.
Figure 11. Handle from disconnect installed onto cover.
8. Mount the filler plate assembly
to the filler supports,
as shown in Figure 12. Secure with four 10-32 x
7
/
16
"
thread-forming screws [11] and tighten to 22 in.-lb.
Figure 12. Mounting the filler plate assembly on the supports.