Data Sheet
October 1, 2009

Austin Lynx

TM

II

12V SIP Non-isolated Power Modules:

8.3 – 14Vdc input; 0.75Vdc to 5.5Vdc Output; 10A output current

LINEAGE

POWER

12

Feature Description

Remote On/Off

The Austin Lynx

TM

II SMT power modules feature an

On/Off pin for remote On/Off operation. Two On/Off
logic options are available in the Austin Lynx

TM

II series

modules. Positive Logic On/Off signal, device code
suffix “4”, turns the module ON during a logic High on
the On/Off pin and turns the module OFF during a logic
Low. Negative logic On/Off signal, no device code
suffix, turns the module OFF during logic High on the
On/Off pin and turns the module ON during logic Low.

For positive logic modules, the circuit configuration for
using the On/Off pin is shown in Figure 27. The On/Off
pin is an open collector/drain logic input signal (Von/Off)
that is referenced to ground. During a logic-high (On/Off
pin is pulled high internal to the module) when the
transistor Q1 is in the Off state, the power module is
ON. Maximum allowable leakage current of the
transistor when Von/off = V

IN,max

is 10µA. Applying a

logic-low when the transistor Q1 is turned-On, the power
module is OFF. During this state VOn/Off must be less
than 0.3V. When not using positive logic On/off pin,
leave the pin unconnected or tie to V

IN.

Q1

R2

R1

Q2

R3

R4

Q3

CSS

GND

VIN+

ON/OFF

PWM Enable

+

_

ON/OFF

V

I

ON/OFF

MODULE

Figure 27. Circuit configuration for using positive
logic On/OFF.

For negative logic On/Off devices, the circuit
configuration is shown is Figure 28. The On/Off pin is
pulled high with an external pull-up resistor (typical R

pull-

up

= 68k, +/- 5%). When transistor Q1 is in the Off state,

logic High is applied to the On/Off pin and the power
module is Off. The minimum On/off voltage for logic
High on the On/Off pin is 2.5Vdc. To turn the module
ON, logic Low is applied to the On/Off pin by turning ON
Q1. When not using the negative logic On/Off, leave
the pin unconnected or tie to GND.

Q1

R1

R2

Q2

CSS

GND

PWM Enable

ON/OFF

VIN+

ON/OFF

_

+

V

I

MODULE

pull-up

R

ON/OFF

Figure 28. Circuit configuration for using negative
logic On/OFF.


Overcurrent Protection

To provide protection in a fault (output overload)
condition, the unit is equipped with internal
current-limiting circuitry and can endure current limiting
continuously. At the point of current-limit inception, the
unit enters hiccup mode. The unit operates normally
once the output current is brought back into its specified
range. The typical average output current during hiccup
is 3.0A.

Input Undervoltage Lockout

At input voltages below the input undervoltage lockout
limit, module operation is disabled. The module will
begin to operate at an input voltage above the
undervoltage lockout turn-on threshold.

Overtemperature Protection

To provide protection in a fault condition, the unit is
equipped with a thermal shutdown circuit. The unit will
shutdown if the thermal reference point T

ref

, exceeds

125

o

C (typical), but the thermal shutdown is not

intended as a guarantee that the unit will survive
temperatures beyond its rating. The module will
automatically restarts after it cools down.