GE Industrial Solutions Spectra Series Power Panelboards AMC6EY and AMC6QB User Manual

Spectra series™ power panelboards, General, Installation

Advertising
background image

g

Spectra Series™ Power Panelboards

Circuit Breakers and Modules

WARNING:

Danger of electrical shock or injury.

Turn

OFF power ahead of the panelboard or

switchboard before working inside the
equipment or removing any component

.

Do

not remove circuit protective devices or any
other component until the power is turned
OFF.

General

These instructions apply to the following catalog numbers:

•Circuit breaker modules AMC6EY and AMC6QB
•Circuit breaker frames TEY, THQB, and THHQB

Installation

1. Prepare the module.

Attach the filler supports to each

end of the module using the #10-32

x

3

/

4

"

hex-head

screws, as shown in Figure 1. Tighten the screws to
15–20 in.-lbs. Loosen the latch-locking screws.

2. Install the circuit breaker(s).

Hook the load end of the

circuit breaker onto the module and secure with the
captive screws on the line end, as shown in Figure 1.
Tighten the screws to 25 in.-lbs.

3. Install the module.

Fully retract the latches on the end

of the module, shown in Figure 1, and hook one side
of the module on the interior rail. Release the latch.
Pivot the module onto the bussing and engage the
second latch. Release the latch. Tighten the latch
screws to 25 in.-lbs., as shown in Figure 2.

Figure 1. Installing the circuit breaker on the module.

Figure 2. Attaching the circuit breaker module to the panelboard

interior.

4. Wire the circuits.

Refer to the rating label on the

circuit breaker for the proper tightening torques.

5. Filler plate kits.

Install the appropriate filler plate kit

as listed in Table 1.

Breaker Module

Filler Plate Kit

AMC6EY

AFP3EYD

AMC6QB

AFP3QBD

Table 1. Filler plate kit for each breaker module type.

Attention – Procedure for Aluminum
Terminations

1.

Strip the insulation, being careful to not nick the wire.

2.

Clean the wire strands with a wire brush.

3.

Thoroughly coat the stripped conductor with a
suitable antioxidant compound, such as ALNOX or
PENETROX A13.

4.

Insert the conductor and tighten the connector screw
to the torque indicated on the rating label.

GEH5677 Installation Instructions

R03

Circuit

Breaker

Filler

Support

#10-32

Screw

Filler

Support

Load-End

Connection

Captive

Screws

Latch

Latch

Screw

Latch

Screw

Latch

Advertising