Technical specifications – GE Industrial Solutions EP0300AC48TEZ User Manual

Page 2

Advertising
background image

GE Critical Power reserves the right to make changes to the product (s) or information contained herein without notice. No liability is assumed as a result of their use or

application. No rights under any patent accompany the sale of any such product(s) or information.

©

2013

GE Critical Power (Bangalore, India) All Rights Reserved.

Document Rev No: R0.1 Date: 5

th

February 2013

PDF name: EP0300AC48TEZ PDS.pdf

Technical Specifications

Input Parameters

Operating Voltage range

90-290 Vac

Disconnect: < 90Vac & > 290Vac
No damage up to 300Vac

Full Power input voltage
Range

90-290 Vac

Frequency

45 to 65Hz

Maximum Current

4A (rms) 230Vac,100% load

Power Factor

> 0.99 at 230Vac,100% load

Total Current Harmonic

Distortion (THD)

< 10% at 230Vac,100% load

Efficiency

≥ 90%. 230Vac,100% load

Input protection

In built surge protection (2kV/3kA)

Inline

fuse



Output Parameters

Voltage, nominal

48 Vdc

Voltage adjust range

42 … 57 Vdc (controller)

Rated output Power

300W

Output Current @...V

5.5A@54V

Maximum current

6.25A

Static Voltage regulation

±1% from 10% to 100% load

Noise (Ripple + spikes)

≤ 100 mV

rms

Load sharing

10%

I/P and O/P connector

Rear side

Output protection

Over voltage shutdown
Blocking diode

Short circuit proof
Over temperature protection

Note:

As a result of continuous product improvement, all specifications are subject to change without prior notice. All performance parameters are valid at Nominal input (230Vac) and nominal output

(48Vdc) conditions unless otherwise specified.

Applicable Standards

Electrical safety

IEC 60950-1

UL

60950-1

CSA

22.2

EMI

As

per

CISPR-22

EMC

IEC 61000-4-5, (Surge immunity limits)

IEC 61000-4-6, (RF Conducted susceptibility immunity limits)

IEC 61000-4-3, (Radiated Electromagnetic Field immunity limits)

IEC 61000-4-4, (EFT/ Burst immunity limits)

IEC 61000-4-2, (ESD Immunity limits)

Harmonics

EN 61000-3-2

Environment

RoHS compliant

Ordering Information

Product Description

Comcode

EP0300AC48TEZ

48V, 300W rectifier

150022411

Country of Sale

South Asia

India

SE Asia

-

NA -
CALA

-

European

-

Other Parameters

Isolation

3.0 kVac – I/P & O/P
1.5 kVac – input & earth
0.5 kVac – output & earth

Visual Indications

Normal LED (Green):
3 status (Blink, OFF, ON)
Fault LED (Red):
3 status (Blink, OFF, ON)

Operating temp

-25°C to +75°C

Power De-rating

+60°C to +75°C

Operating Humidity

5% to 95% RH non-condensing

MTBF

> 150k hours Telcordia SR-332,

Method 1, Case 3 (Ambient

Temperature.: 25°C)

Audible Noise

< 60dBA at an ambient noise level of
45dBA, and at ambient temperature
of 25°C

Mechanical

Width

50.4 mm (2”)

Height 45

mm

(1.75”)

Depth 228.6mm

(9”)

Weight

0.5 kg (1.1 lbs)