Preliminary Data Sheet

ACE184 Series Power Shelf

Main Output: 600A; Standby output: 8A

October 29, 2012

©2012 General Electric Company. All rights reserved.

Page 2

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings
only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations

sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.

Parameter

Device

Symbol

Min

Max

Unit

Operating Ambient Temperature

All

TA

-10

70

°C

Storage Temperature

All

Tstg

-40

85

°C


Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions.

Parameter

Device

Symbol

Min

Typ

Max

Unit

OUTPUT
Main output

All

I

out

0

600

A

dc

Standby Output

All

I

out

0 8 A

dc

Isolation

1

Output - Ground

All

500

V

dc


Port

Phenomena

test

criteria

Reference standard

Enclosure

ESD (immunity)

8 kVair 4 kVcontact

A

EN 61000-4-2

1

Isolation in the context of this data sheet documents the capability of the shelf. Actual isolation capability may be further reduced by the isolation

capability of the utilized modules. Consult the module data sheet for actual capability.