Geh-5643p2, Attention – procedure for aluminum terminations – GE Industrial Solutions Spectra Series Power Panelboards AMC6QD and AMC4QD User Manual

Page 2

Advertising
background image

Figure 4. Installing the breaker on the module.

4. Position the module.

Loosen the latch lock screws and

fully retract the latches. Line up the guide fingers on
both ends of the module with the notches in the
panelboard interior rails, as shown in Figure 5. Allow
no space between units.

Figure 5. Positioning the breaker module.

5. Install the module.

Latch one side of the circuit

breaker module. Release the rail latch. Pivot the
module onto the bus bars and engage the second
latch. Release the rail latch. Tighten the rail latch
screws to 25 in.-lbs, as shown in Figure 6.

Figure 6. Installing the breaker module.

6. Wire the circuits.

Refer to the label on the circuit

breaker for the proper tightening torque. levels

7. Filler plate kits.

Install filler plate kits, as listed in

Table 1.

Filler Plate

Cat. No.

Module Type

AFP3QDD

AMC6QD

AFP2QDD

AMC4QD

Table 1. Filler plate kit for each breaker module type.

Attention – Procedure for Aluminum
Terminations

1.

Strip the insulation, being careful to not nick the wire.

2.

Clean the wire strands with a wire brush.

3.

Thoroughly coat the stripped conductor with a
suitable antioxidant compound, such as ALNOX or
PENETROX A13.

4.

Insert the conductor and tighten the connector screw
to the torque indicated on the rating label.

Stud

Post

1

/

4

-20 Screw &

Conical Washer

#10-32 Screw

Filler

Support

Latch Lock

Screw

Latch

Latch Lock

Screw

Latch

Advertising