Terminal assemblies are supplied with the
Entelliguard breaker. Fixed breakers have Back or
Front Connected Terminations available. This
instruction is for Back Connected Terminations





































Back Connected Terminations Assembly mounting
Procedure:


1. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the

breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background.


2. Assemble the outer bottom & top Back

Connected Terminations assemblies first on to
the breaker terminals & orient them as shown in
fig A.


3. Terminal assemblies to be tightened with M12

hardware’s as shown in Fig A, to 80 Nm (59 ft-lbs)
torque.


4. Assemble the heat sinks LH & RH on the outer

poles first, and tightened them with M6

hardware’s to 8Nm (5.9 ft-lbs) torque as shown in
fig B.

5. Repeat the above mounting procedure for the

adjacent poles.

6. Assemble remaining terminal assemblies similarly

on all poles so as to populate as 3pole / 4 pole
breaker fig C & D.


7. The bus bars to be supported within 200mm

distance and tightened to 80Nm (59 ft-lbs) torque

Envelope Size Catalog #

TYPE

GBB230TBB3 3

pole

Envelope2

GBB230TBB4 4

pole

EntelliGuard

®

G

Circuit Breaker

Accessories
Back Connected Terminations for Fixed

Breaker

WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation, et décharger les

resorts d’armement

DEH- 41439 Installation Instructions

M12 Hardware

M12 Spring
washer

M12 Plain
washer

Terminal
Assembly

Nut plate

M12 Hardware

M12 Spring
washer

M12 Plain
washer

Terminal
Assembly

Nut plate

Fig A. Back Connected Terminations assembly
for 3000 Amperes (UL)

Table 1. Back Connected Terminations