17

Cat. No.

List Price,

GO-10CB

Cat. No.

List Price,

GO-10CB

451WPS20H

$817.97

451WPS40H

$1,351.42

Description

480W power supply, 24V 20A

960W power supply, 24V 40A

Dimensions (mm) W x H x D

240 x 153 x 86

292 x 185 x 130

Input
Nominal input voltage

3 x 360 500V AC, 47 63 Hz

3 x 360 500V AC, 47 63 Hz

Input voltage range

3 x 340 550V AC, 47 63 Hz

3 x 340 550V AC, 47 63 Hz

Nominal input current

3 x 1.5A at 3 x 400V AC

3 x 3A at 3 x 400V AC

Input current peak

< 50A

< 50A

Power factor cos w

0.53 capacitive at 400V AC

0.53 capacitive at 400V AC

Output
Output voltage

24V DC ±1%

24V DC ±1%

Typical setting range

22.5-27.5V DC

22.5-27.5V DC

Output direct current

0 20A

0 40A

Ripple

< 100 mV

< 100 mV

Typical current limitation

25A

45A

Parallel operation

Yes

Yes

Efficiency, typical

90%

90%

Hold-up time

> 5 ms / 400V AC

> 5 ms / 400V AC

Line regulation

< 0.2% at UON ±15%

< 0.2% at UON ±15%

Load regulation

< 1% at 0A -> >I

nominal

< 1% at 0A -> >I

nominal

Dynamics

< 2 ms at 10 < > 90% I

nominal

, overshoot < 2%

< 2 ms at 10 < > 90% I

nominal

, overshoot < 2%

Current limitation

Permanently short-circuit proof

Permanently short-circuit proof

Overrun-proof/open-circuit proof

Yes

Yes

Output overcurrent switch-off

Yes

Yes

Output security

VDE 0805/EN 60950/IEC 950/UL 1959
Safety extra-low voltage (SELV) EN 60950

VDE 0805/EN 60950/IEC 950/UL 1959
Safety extra-low voltage (SELV) EN 60950

Class of protection

Class I

Class I

Degree of protection

IP 20

IP 20

Leakage current

< 3.50 mA (47 -63 Hz mains frequency)

< 3.50 mA (47 -63 Hz mains frequency)

Ambient temperature

0 °C...+70 °C at free convection

0 °C...+70 °C at free convection

Power derating

2.5%/k from +60°C

2.5%/k from +60°C

Storage temperature

25°C...+85°C

25°C...+85°C

EMC CE-certified

EN 50081-1/-2, EN 50082-1/-2

EN 50081-1/-2, EN 50082-1/-2

Radio interference suppression

EN 55011/EN 55022 class B

EN 55011/EN 55022 class B

Static discharge ESD (IEC 1000-4-2)

8 kV contact discharge, 15 kV air discharge

8 kV contact discharge, 15 kV air discharge

Electromagnetic fields (IEC 1000-4-3) 10V/m

10V/m

Burst (IEC 1000-4-4)

4 kV input, 2 kV output / capacitive coupling

4 kV input, 2 kV output / capacitive coupling

Surge (IEC 1000-4-5)

4 kV unbalanced, 4 kV balanced

4 kV unbalanced, 4 kV balanced

Conducted interference type
(ENV 50141, IEC 1000-4-6)

10V, 150 kHz...80 MHz

10V, 150 kHz...80 MHz

Weight

Approx. 1.9 kg

Approx. 3.6 kg

Installation

Snap-on DIN rail fixation DIN EN 50022-35

Snap-on DIN rail fixation DIN EN 50022-35

Installation position

Panel-mounted; input connectors on top, output
connectors at the bottom

Panel-mounted; input connectors on top, output
connectors at the bottom

POWER SUPPLIES – THREE-PHASE SWITCH MODE

451 Series Terminal Blocks

EN 60947-7-1
DIN VDE 0611T1

Advertising