Back Connected Terminations
Cassette Envelope 3

Terminal assemblies are supplied with the
Entelliguard breaker.



































Back Connected Terminations Assembly Procedure:

1. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows

DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
cassette before continuing.


2. Assemble the outer pole bottom & top Back

Connected Termination assemblies first to the
cassette back terminal support as shown in Fig A.


3. Terminal assemblies to be tightened with M10

hardware’s as shown in Fig A, to 40 Nm (29.5 ft-
lbs) torque.


4. Assemble the heat sinks LH & RH as shown in Fig

B on the outer poles first, and tightened them to

14 Nm (10.3 ft-lbs) torque.


5. Repeat the above mounting procedure for

remaining adjacent poles.

6. Assemble remaining terminal assemblies similarly

on all the poles so as to populate as 3pole / 4 pole
breaker fig C & Fig D.


7. The bus bars to be supported within 200mm

distance and tightened to 80Nm (59 ft-lbs) torque

Envelope Size Catalog # Description TYPE

GBB360TBC3 Top side 3 pole

GBB360BBC3 Bottom side 3 pole

GBB360TBC4 Top side 4 pole

Envelope 3

GBB360BBC4 Bottom side 4 pole

EntelliGuard

®

G

Circuit Breaker

Accessories
Back Connected Terminations for
Cassette

WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation, et décharger les

resorts d’armement

DEH-41437 Installation Instructions

Top
terminal
Asm

Bottom
terminal
Asm

M10 Plain
washer

M10 spring
washer

M10 hardware
40 Nm Torque

Top
terminal
Asm

Bottom
terminal
Asm

M10 Plain
washer

M10 spring
washer

M10 hardware
40 Nm Torque