Spectra Series™ Power Panelboards

Type ANK Neutrals (Model 2)

Installation

WARNING: Danger of electrical shock or injury.
Turn

OFF power ahead of the panelboard or

switchboard before working inside the equipment or
removing any component

.

Equipment is to be

installed and maintained by properly trained and
qualified personnel only.

1. Mount the neutral at either location in the end of the

panelboard enclosure marked

NEUTRAL

on the

1

/

4

-20

mounting studs, as shown in Figure 1. Secure with the flat
washer, lock washer, and nut provided and tighten to
27–32 in-lb.

Figure 1. Mounting locations on the panelboard enclosure.

Figure 2. Securing the neutral to the panelboard.

2. Fasten the opposite end of the neutral to the enclosure

with two 10-32 x

11

/

16

" thread-forming screws provided.

Tighten to 27–32 in-lb. Figure 3 shows the neutral
mounted to the back wall of the enclosure.

Figure 3. Neutral mounted to the back wall of the enclosure.

3. When a bonding strap is required for service entrance

applications, first loosen the wire connector nuts at the
positions indicated in Figure 3. Slide the bond strap
provided with the neutral under the connector, then
retighten the nuts to 200–250 in-lb.

NOTE: If the box is painted, scratch through the paint in the
area where the bonding strap is in contact with the enclosure.

4. Secure the bond strap to the enclosure with the 10-32 x

3

/

8

" SEMS screw provided. Tighten to 27–32 in-lb. The

installation of the neutral is now complete.

Neutral with Ground-Fault Sensor

5. To mount a neutral with ground-fault sensor, complete

steps 1–4. To test the installation, do the following:

• 800–1200 A: Loosen the

3

/

8

-16 nuts, as shown in

Figure 4, and remove the connector strap. After testing,
reassemble and tighten the nuts to 14 ft-lb.

• 400–600 A: loosen the

3

/

8

-16 nuts, as shown in Figure

5, and remove the sensor. After testing. reassemble and
tighten the nuts to 14 ft-lb.

GEH5585 Installation Instructions

R05

Install this box end

toward main

incoming line

(supply) cables