External Accessories

• Motor-operated mechanisms
• Back-connected studs
• Plug-in and bolt-on bases for 100%-rated breakers
• Mechanical interlocks
• Padlocking devices

• Handle operator

– TDA: flange mounted, variable depth
– TDM: door mounted, variable depth
– TDR: integral mechanism, fixed depth

For a complete listing of external accessories, see the GE
BuyLog, GEP-1100, and GEP-746.

Trip Unit Selection

MicroVersaTrip Plus™ trip unit functions available in K
Frame breakers are listed in Table 3.

For detailed information on trip unit selection, see GE
publication GEH-6273.

Code

Description

Function

C

Power Break, J Frame, K Frame

Breaker Type

2

2000 A maximum CT

Breaker Frame

08

800 A

Installed

12

1200 A

CT

L

Long-time (standard)

Overcurrent

S

Short-time

Protection

I

Instantaneous

G

Ground fault

Ground Fault Protection

Z1

Ground-fault zone-selective interlock

Optional

Z2

Ground fault and short-time ZSI

Functions

R

Replacement trip unit

Replacement

For single-phase, 3-wire or 3-phase, 4-wire applications, order appropriate
neutral sensor.
Requires purchase of zone-selective interlock module(s) type T1M1 (120
Vac control voltage).

Table 3. Catalog number options for MicroVersaTrip Plus™ trip units available with K Frame circuit breakers.

Rating Plug Selection

Rating plugs available with MicroVersaTrip Plus™ trip
units in K Frame breakers are listed in Table 4.

Frame Type

Sensor Rating, A

Current Rating, A

Rating Plug Cat. No.

300

TR8B300

400

TR8B400

K800

800

500

TR8B500

600

TR8B600

700

TR8B700

800

TR8B800

600

TR12B600K

K1200

1200

800

TR12B800K

1000

TR12B1000K

1200

TR12B1200K

Table 4. Rating plugs available with MicroVersaTrip Plus™ trip units in K Frame breakers.

Test Kit, Cat. No. TVRMS2

The portable, battery-powered test kit provides for
MicroVersaTrip Plus or PM trip unit self-tests and
functional trip/no-trip tests. It also provides for defeat of
the ground-fault function and can be used in conjunction
with high-current test equipment. Interface is via a plug
on the front of the trip unit and tests can be conducted
with the breaker in service. The kit can also be powered
by a 120 Vac source.

Application Information

For information on derating, time-current curves,
inspection, and testing, refer to GE publication GET-
2779.