NB!
Please note the values available within the different standard groups of resistors:

E12: Closest standard value is 470

Ω, creating an input of 449.9Ω and 8.997V.

E24: Closest standard value is 510

Ω, creating an input of 486.4Ω and 9.728V.

E48: Closest standard value is 511

Ω, creating an input of 487.3Ω and 9.746V.

E96: Closest standard value is 523

Ω, creating an input of 498.2Ω and 9.964V.

Analog inputs - terminal X42/1-6
Parameter group for read out: LG-3#. See also AF-600 FP Programming Guide.

Parameter groups for set-up: AO-##, AO-1#, AO-2# and AO-3#. See also AF-600 FP Programming Guide.

3 x Analog inputs

Operating range

Resolution

Accuracy

Sampling

Max load

Impedance

Used as

temperature

sensor input

-50 to +150 °C

11 bits

-50 °C

±1 Kelvin

+150 °C

±2 Kelvin

3 Hz

-

-

Used as

voltage input

0 - 10 VDC

10 bits

0.2% of full

scale at cal.

temperature

2.4 Hz

+/- 20 V

continuously

Approximately

5 kΩ

When used for voltage, analog inputs are scalable by parameters for each input.

When used for temperature sensor, analog inputs scaling is preset to necessary signal level for specified temperature span.

When analog inputs are used for temperature sensors, it is possible to read out feedback value in both

°C and °F.

When operating with temperature sensors, maximum cable length to connect sensors is 80 m non-screened / non-twisted wires.

Analog outputs - terminal X42/7-12
Parameter group for read out and write: LG-3#. See also AF-600 FP Programming Guide
Parameter groups for set-up: AO-4#, AO-5# and AO-6#. See also AF-600 FP Programming Guide

3 x Analog outputs

Output signal level

Resolution

Linearity

Max load

Volt

0-10 VDC

11 bits

1% of full scale

1 mA

Analog outputs are scalable by parameters for each output.

The function assigned is selectable via a parameter and have same options as for analog outputs on control card.

For a more detailed description of parameters, please refer to the AF-600 FP Programming Guide.

Real-time clock (RTC) with back-up
The data format of RTC includes year, month, date, hour, minutes and weekday.

Accuracy of clock is better than

± 20 ppm at 25 °C.

The built-in lithium back-up battery lasts on average of 0 years, when frequency converter is operating at 40

°C ambient temperature. If battery pack back-up

fails, analog I/O option must be exchanged.