Guide Form Specifications

hidden

The microprocessor-based multifunction device shall

provide the functions listed below.

Communications

The device shall be capable of communicating on both

the POWER LEADER commnet and Modbus RTU

communication protocols. It shall communicate all

metering and setup information polled from connected

POWER LEADER commnet devices to a host PC

equipped with Power Management Control System 5.0

software. This shall be a multitasking system, providing

event logging, alarm and event indication, energy

trending, and the collection of information on a

scheduled basis. The device shall also be capable of

communicating setup and control commands from the

host computer to the attached commnet devices.

Inputs/Outputs

The device shall accept input from up to eight POWER

LEADER commnet segments. Each commnet segment

shall support up to four POWER LEADER commnet

devices (not including POWER LEADER Repeaters

and Junction/Outlet Boxes).

The device shall provide RS485 input and output ports

with adjustable baud rate (1200, 2400, 4800 and 9600

baud, and 19.2 Kbaud) for communications on a

Modbus RTU protocol network.
The device shall have a four-character alphanumeric

high-contrast LED display and a four-key keypad on its

faceplate.
The device shall require control power of 85-265 volts

ac or 100-250 volts dc.

Configuration

The device configuration and all user-defined values

and settings shall be entered via the keypad. The device

shall be capable of being automatically configured.

Construction

The device shall be provided in a steel case with

provisions for communications connections on the

front of the case. Control power voltage connections

shall also be made on the front of the case. The device

shall be front mounted via mounting holes provided at

each end of the case.

Host

RS485 connect ion t o
Modbus Concentr at or

POW ER MEASU REMENT LI MITED

3720 AC M

EPM 3710 or 3720

RMS- 9C

Tr ip Unit s

POWER LEADER

El ectr onic Power Meter

MU LTILI N

F EEDER MANAGEMENT RELAY

565

Multilin 565

POWER LEADER

Met er

RMS-9D Tr ip Unit s

GE Fanuc 90/30 or 90/70

Contr ol Power

Commnet segments t o POWER LEADER Commnet devices

Modbus net wor k connect s RS485 native devices

g

POWER LEADER
Modbus® Concentrator

Commnet Connecti ons