GE Industrial Solutions Spectra Series Power Panelboards AEG 10, 21, 21S, 31S User Manual

Spectra series™ power panelboards, Installation

Advertising
background image

g

Spectra Series™ Power Panelboards

Equipment Grounds, Types AEG 10, 21, 21S, 31S

Installation

WARNING:

Danger of electrical shock or injury.

Turn

OFF power ahead of the panelboard or

switchboard before working inside the
equipment or removing any component

.

Equipment is to be installed and maintained by
properly trained and qualified personnel only.

See Figures 1 and 2 for illustrations of AEG10 and AEG21
uninsulated equipment grounds and Figures 3 and 4 for
illustrations of AEG21S and AEG31S insulated equipment
grounds.

1.

Attach terminals to the straps as shown in the
appropriate figure. Find the holes for mounting the
equipment ground at the opposite end of the box
from where it is stamped

Line

. If the box is painted,

scratch through the paint in the area where the strap
is to contact the box. Mount the equipment ground
with the two 10-32 thread-forming screws provided
and tighten to 25-30 in-lb.

2.

Remove the paper backing from the identification
label provided. Place the label below the equipment
ground, approximately in the position shown.

Figure 1. Equipment ground catalog number AEG10.

Figure 2. Equipment ground catalog number AEG21.

Figure 3. Equipment ground catalog number AEG21S.

GEH5586 Installation Instructions

R02

Mounting

Positions

Identification

Labels

Mounting

Positions

Identification

Labels

Mounting

Positions

Identification

Labels