ZTSCT / ZBTSCT Operation & Maintenance Manual

Installation

Table 2

Tightening Torque for Lugs

Socket Size

Across Flats

Torque

Lb. - In.

Lb. - Ft.

45

1/8

4

100

5/32

8

120

3/16

10

150

7/32

12

200

1/4

17

275

5/16

23

375

3/8

31

500

1/2

42

600

9/16

50

D

CABINET

LIFTING EYES

SPREADER BAR

H

45°

Figure 1

Power Connections

GE Zenith transfer switches are supplied with UL listed
solderless screw type terminals as standard for the Source 1,
Source 2 and Load power connections. Table 1 lists the
number and sizes of cable lugs supplied as standard for
each switch amp rating.

Connect the Source 1, Source 2, and Load conductors
to the clearly marked terminals on the transfer switch.
Remove surface oxides from cables by cleaning with a
wire brush. Verify that all connections are correct before
tightening the lugs. All cable lug connections must be
tightened to the proper torque values as shown in Table 2.

NOTE

:

Do not run cables or wiring behind
front-connected transfer switches.

Engine Start
Control Connections

Engine-start control wires connect to control terminals
beside the MX250. Engine start terminals are indicated
by a schematic symbol (the symbol indicates the contact
state for a de-energized normal source). Figure 3 shows
the engine-start contacts.

Make all other necessary control connections to the control
panel terminal blocks per the schematics supplied with
the ATS.

NOTE

:

All control wires (18-12 AWG) must be
torqued to 19 in/lbs.

NOTE

:

When lifting the switch using a spreader bar,
height H must be equal to half of distance D.

Table 1

Power Connections: Screw Type Terminals for External Power Connections

Switch Size

(Amps)

40

80

100

150

200, 225, 2500

260, 300*, 400

600

800, 1000, 1200

Source 1, Source 2 & Load Terminals

1

#8 AWG to 1/0

Cable Per Pole

Range of Wire Sizes

1

#8 AWG to 1/0

1

#8 AWG to 1/0

1

#8 AWG to 3/0

1

#6 AWG to 250 MCM

1

#4 AWG to 600 MCM

2

#2 AWG to 600 MCM

4

#2 AWG to 600 MCM

Neutral Bar (When Required)

3

#8 AWG to 1/0

No. of Cables

Range of Wire Sizes

3

#8 AWG to 1/0

3

#8 AWG to 1/0

3

#8 AWG to 300 MCM

3

#6 AWG to 300 MCM

3

#4 AWG to 300 MCM

8

#2 AWG to 600 MCM

12

#2 AWG to 600 MCM

1600, 2000

2600, 3000, 4000

Line, Load and Neutral terminals are located in the rear of switch

and arranged for bus bar locations

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

DANGER