Terminal board points, 1 digital inputs terminal board points, 2 relay outputs terminal board points – GE Industrial Solutions D8R4 expanded I_O for AV-300i Drives User Manual
Page 7
7
—————— I/O Expansion card ——————
D8R4
3. TERMINAL BOARD POINTS
3.1 DIGITAL INPUTS TERMINAL BOARD POINTS
Connectors XDI0 and XDI1 have different ground connection.
Connector
Terminal
31
32
33
34
35
36
37
38
39
40
Function DI0 DI1 DI2 DI3 GND DI4 DI5 DI6 DI7 GND
exp10
DIGITAL INPUTS
XDI1
XDI0
3.2 RELAY OUTPUTS TERMINAL BOARD POINTS
Relay outputs need a +24V (60mA) supply voltage.
The Drive TB can be used to supply 24VDC power. AV-300i 24VDC supply
maximum output = 120 mA total including Encoder, LAN, Expansion card and
DGF (or 350 mA without DGF).
Connector
Relay
Terminal
114
111
112
214
211
212
Function N.Open
COM N.Closed N.Open
COM N.Closed
Connector
Relay
Terminal
314
311
312
414
411
412
Function N.Open
COM N.Closed N.Open
COM N.Closed
exp20
R2
R3
RELAY OUTPUTS
RELAY OUTPUTS
XCQ1
XCQ0
R0
R1
Connector
Terminal
100
101
Function
0V power supply
+24V power supply
exp30
RELAY OUTPUTS POWER SUPPLY
XSC