GE Industrial Solutions SLI Inverters User Manual

Page 2

Advertising
background image

2

Lineage Power

Data Sheet

SLI Inverters

February 2010

High-Efficiency, Low-Profile 1500 VA Inverters

Specifications

Electrical

Input Voltage

48 VDC (40-72 VDC) or 24 VDC (20-36 VDC)

Output Voltage

115 VAC (100-120 VAC) or 230 VAC (200-240 VAC) - select 115 or 230 VAC

model

Output Power

1500 W

Output Waveform

True sine wave

Frequency

50/60 Hz (47-63 Hz) - select 50 or 60 Hz model

Frequency (Stability)

±0.02% maximum

Inverter Technology

Pulse Width Modulation /High Frequency Switching

Dielectric Strength

2,500 VAC minimum

Inrush Current

<10 A

Operating Modes

On-line (standard); Standby (selectable)

Efficiency

peak efficiency 93%

Output Power Factor

0.33 lagging or leading

Total Harmonic Distortion

2% maximum for linear loads /<3% for non-linear loads

DC Noise Feedback

< 30 dBrnc

Transient Response

<3% voltage change on instantaneous 0 to 100% load change

Transfer Time (With Static Switch)

< 2 msec

Overload Capacity

up to 125% continuous; 125% to 150% - 1800 cycles, 150% to 220% - 24

cycles, 220% to 300% - 4 cycles

Load Voltage Regulation

+3%/-1%

Communications

RS-485 or CANBUS communications interface and photo alarm relay

Display

2 x 20 LCD display (optional) with LED status bar

Input Overvoltage Protection

48 Vdc models: 74V; 24 Vdc Models: 37V

Input Undervoltage Protection

48 Vdc models: 36V; 24 Vdc Models: 18V

Input Overcurrent Protection

48 Vdc models: 70A; 24 Vdc models: 140A

Overload

230 Vac models: 1800 VA; 115 Vac Models: 1650 VA

Surge Capacity

230 Vac models: 2300 VA for 200 ms; 115 Vac Models: 1750 VA for 200 ms

Electronic Overcurrent Protection

230 Vac Models: 1A to 8A (selectable); 115 VAC Models: 2A to 15A (selectable)

AC Circuit Breaker

230 Vac Models: 10A; 115 Vac Models: 15A

Electronic Short-circuit Protection: 230 Vac Models: 30A; 115 Vac Models: 60A
Protection Mode

Progammable for "latch" or "auto restart" after incident

Isolation

PRI-SEC: 3000 Vrms PRI-GND: 1000 Vrms SEC-GND: 1500 Vrms Signal-GND: 0

Vrms

MTBF

200,000 hours at 40°C

Advertising