GE Industrial Solutions GT Series UPS programmable relay card User Manual

Programmable relay i/o card user manual, Presentation, Technical specification

Advertising
background image

PROGRAMMABLE RELAY I/O CARD

USER MANUAL

PRESENTATION

FEATURES
This relay I/O card is an UPS management
product with 6 relay output contacts for monitoring
UPS status and 1 input contact as shutdown UPS
or test battery command.
Features:

UPS status information presented as 6

contact closures and they are changable.

Programmable output contacts, monitors the

UPS events that users really concern in
different practices.

Customized normal open or normal close for

individual relay.

Configurable UPS shutdown delay time.
Configurable input signal as shutdown UPS or

battery test.

Has the ability to protect up to 6 computers

unattended shutdown gracefully.

TECHNICAL SPECIFICATION

TECHNICAL SPECIFICATION

Size

130 x 60 mm

Weight

200 g

Operating Temperature 0 ~ 40

° C

Operating Humidity

10 ~ 80 %

Power Input

8 ~ 20V DC

Power Consumption

1.2 Watts


OUTPUT CONTACT RATING

Maximum

DC Voltage DC Current

Relay
R1~R6

24 V

1A


INPUT RATING

Maximum

DC Voltage DC Current

Input

24 V

10 mA

APPLICATION EXAMPLE

In this case we’ll adopt the default settings, please
keep SW1 and SW2 to OFF position. Provide less
than 24VDC to Common contact and connect the
lamps to R1~R6 terminals. Press the button over
3 seconds to shutdown UPS remotely.

Common

GND-R

R1

R2

R3

R4

R5

Input

+12V

Summary Alarm

Power Fail

Battery Low

On Bypass

Overload

Shutdown UPS

R6

Over Temperature

INTERNAL CIRCUIT

R1

R2

R3

R4

R5

Common

GND-R

Input

+5V

CPU Pin

R6


OUTLINE

GND-R
Common
R1
R2
R3
R4
R5
R6
Input
Tx
Rx
GND-C

SW1
SW2


I/O PINOUT
GND-R
: Ground for relays
Common: 12~24VDC
Default

Alarm

Event

R1 Summary

Alarm

R2 Power

Fail

R3 Battery

Low

R4 On

Bypass

R5 Overload
R6 Over

Temperature

Input: Remote shutdown or battery test
Tx: Transmit to PC, connect to sub9-pin2
Rx: Receive from PC, connect to sub9-pin3
GND-C: Ground for configuration Tx and Rx pins

OFF (Default) ON

SW1 Normal

open

for default settings

Normal close
for default settings

SW2 Default settings

Customized settings

PROGRAMMABLE CONTACTS

COMMUNICATION SETUP
1. Connect

Tx to pin2, Rx to pin3 and GND-C to

pin5 of PC RS232 port.

2. In Windows environment, launch Hyper-

Terminal application then open the specified
COM port.

3. Set the following properties:
Baud

rate:

2400, Data Bits: 8, Parity: None

Stop

Bit:

1, Flow Control: None


CONFIGURATION
1. Press <Enter> to get the main menu from

Relay I/O card.

+---------------------------+
| UPS Relay Card |
+---------------------------+
Firmware Version: Relay Card V1.4
[1].Customize Output Relay
[2].Configure Input Signal
[3] Customize Normal Open or Normal Close
[0].Quit

Please Enter Your Choice =>

2. Press ‘1’ to configure the alarm event for

R1~R6.
In this menu, contacts R1~R6 are allowed to
assign to different power events.

+
|

---------------------------+
Customize Output Relay |

+---------------------------+
Relay Selected Event
[1].Relay1: Summary Alarm
[2].Relay2: Power Fail
[3].Relay3: Battery Low
[4].Relay4: On Bypass
[5].Relay5: Overload
[6] Relay6: Over Temperature
[0].Back To Previous Menu

Please Enter Your Choice =>

After finishing the configuration please switch
SW2 to ON position to apply your settings,
switch SW2 back to OFF position to apply
default settings.

3. Press ‘2’ to configure the Input signal.

+---------------------------+
| Configure Input Signal |
+---------------------------+
[1].Act as Shutdown or Test: Shutdown
[2].Input Signal Confirm: 3 Seconds
[3].Delay Before Shutdown: 30 Seconds
[0].Back To Previous Menu

Please Enter Your Choice =>

In this menu, the input signal can be redefined
as shutdown UPS or battery test signal.
Meanwhile, the UPS shutdown delay time is
also adjustable to maximum 9999 seconds.

4. Press ‘3’ to configure the normal open or

normal close for each relay.

+---------------------------+
| Customize Output Relay |
+---------------------------+
Relay Selected Event
[1].Relay1: Normal Close
[2].Relay2: Normal Open
[3].Relay3: Normal Close
[4].Relay4: Normal Open
[5
[6

].Relay5: Normal Close
].Relay6: Normal Open

[0].Back To Previous Menu

Please Enter Your Choice =>

Switch SW2 to ON position to apply your
settings. If the SW2 is backed to OFF position
to apply default settings then you can use
SW1 to control normal open or normal close
for all relays.

5. Press ‘0’ to quit this configuration session.

The system would prompt you to save or not.
Press ‘Y’ to save your settings, ‘N’ to ignore.

POWER OPTION IN WIN 2000/XP

This relay card has the ability to provide UPS
signals for Windows NT4/2000/XP/2003. Firstly
please connect the RS232 port from your PC to
the relay card shown as the following.
Then open the power option from control panel
and click on the UPS tab to setup the signals
polarity, select Positive for Power Fail, Low

Battery and UPS
Shutdown.
Because the
R1~R6 contacts
are programmable,
we can configure
the output
contacts for 3
computers with 2
signals (power fail
and low battery) or
6 computers with
one signal (power
fail or low battery).


Note: To ensure all of the protected computers
have the same ground level, it is required to
connect their input power to the same UPS.

Common

GND-R

R1

R2

R3

R4

R5

Input

Power Fail

R6

Battery Low

RTS pin7

GND pin5

CTS pin8

DCD pin1

DTR pin4

Shutdown UPS