Terminal board points, 1 digital inputs terminal board points, 2 digital outputs terminal board points – GE Industrial Solutions D20A6 expanded I_O for AV-300i Drives User Manual

Page 7: 3 analog inputs terminal board points

Advertising
background image

7

—————— I/O Expansion card ——————

D20A6

3. TERMINAL BOARD POINTS

3.1 DIGITAL INPUTS TERMINAL BOARD POINTS

Connectors XDI0 and XDI1 have different ground connection.

Connector

Terminal

31

32

33

34

35

36

37

38

39

40

Function DI0 DI1 DI2 DI3 GND DI4 DI5 DI6 DI7 GND

Connector

Terminal

41

42

43

44

45

Function DI8 DI9 DI10 DI11 GND

expDA10

DIGITAL INPUTS

XDI1

XDI0

XDI0

3.2 DIGITAL OUTPUTS TERMINAL BOARD POINTS

Digital outputs need a +15V…+24V supply voltage. The Drive TB can be used
to supply 24VDC power. AV-300i 24VDC supply maximum output = 120 mA
total including Encoder, LAN, EXP card and DGF (or 350 mA without DGF).

Terminal 60 is power supply, terminal 55 is the common power supply.

Connector

Terminal

51

52

53

54

55

56

57

58

59

60

Function DQ0 DQ1 DQ2 DQ3 COM DQ4 DQ5 DQ6 DQ7 PWR

expDA20

* = Reserved

DIGITAL OUTPUTS

XQD

3.3 ANALOG INPUTS TERMINAL BOARD POINTS

Differential analog inputs are available.

Connector

Terminal

1

2

3

4

5

Function

AI0+

AI0-

AI1+

AI1-

GND

expD30

ANALOG INPUTS

XAI

Advertising