GE Industrial Solutions EAK guidelines User Manual
Page 16
00353
G R O U N D I N G O F T H E
F I L T E R S
The connection between device ECF and derivation point must have at maximum a length of 50
inches).
The grounding terminal of the ECF filter
must be directly connected to the ground bus of the cabinet. In case of
inverter, the same grounding terminal should be also connected to one of the two grounding’s terminals of the
inverter.
M O U N T I N G S E Q U E N C E O F T H E F I L T E R S : S U M M A R Y T A B L E
Device
LINE REGEN
FN COMPACT -RANGER
ECF
MAINS-FILTER-INDUCT~CE-DEVICE
MAINS-INDUCTANCE-FILTER-DEVICE
MAINS-FILTER-INDUCTANCE-DEVICE
Filtering connection using FN, COMPACT or RANGER filters:
Mains supply
Choke
Filter
Figure 5. I: lnverter
Mains supply
Filter
Choke
DV300
Figure 5.2: Converter
Mains supply
Filter
Choke
. RS300
Figure 5.3: line Regen Converter