Electrical specifications, Isolation specifications, General specifications – GE Industrial Solutions QPW025A0F41_H User Manual

Page 3: Continued)

Advertising
background image

Data Sheet

October 5, 2009

QPW025A0F41/QPW025A0F41-H DC-DC Power Module

36-75Vdc Input; 3.3Vdc Output Voltage; 25A Output Current

LINEAGE

POWER

3

Electrical Specifications

(continued)

Parameter

Symbol

Min

Typ

Max

Unit

Output Voltage Set-point

V

O, set

3.24 3.3 3.36 %

V

O, set

(V

IN

=V

IN,nom

, I

O

=I

O, max

, T

ref

=25°C)

-1.6 +1.6

%

V

O, set

Output Voltage

V

O

3.2 - 3.4 %

V

O

(Over all operating input voltage, resistive load,
and temperature conditions until end of life)

Output Regulation

Line (V

IN

= V

IN, min

to V

IN, max

)

0.05 0.2 %

V

O, nom

Load (I

O

= I

O, min

to I

O, max

)

0.05 0.2 %

V

O, nom

Temperature (T

ref

=T

A, min

to T

A, max

)

0.15 0.50 % V

O, nom

Output Ripple and Noise on nominal output

(V

IN

=V

IN, nom

and I

O

= I

O, min

to I

O, max

,

C

out

= 1μF ceramic // 10μF Tantalum capacitor)

RMS (5Hz to 20MHz bandwidth)

10 20 mV

rms

Peak-to-Peak (5Hz to 20MHz bandwidth)

45 60 mV

pk-pk

External Capacitance

C

O

0

10000

μF

Output Current

I

o

0 25

A

dc

Output Current Limit Inception (Hiccup Mode)
(V

o

= 90% V

o, set

)

I

O, lim

105 120 130 % I

o, max

Output Short-Circuit Current

I

O, s/c

130 150 %

I

o, max

V

O

≤ 250 mV @ 25

o

C

Efficiency

V

IN

= 48V, T

A

=25°C, I

O

= I

O, max

A

η

92.5

%

Switching Frequency

f

sw

300

KHz

Dynamic Load Response

(dI

O

/dt=0.1A/

μs; V

IN

=V

IN

,

nom

; T

A

=25°C)

Load change from I

O

= 50% to 75% of I

O, max

Peak Deviation

V

pk

5

% V

O

Settling Time (V

O

<10% peak deviation)

t

s

150

μs

Load change from I

O

= 50% to 25% of I

O, max

,

Peak Deviation

V

pk

5

% V

O

Settling Time (V

O

<10% peak deviation)

t

s

150

μs

Isolation Specifications

Parameter

Symbol

Min

Typ

Max

Unit

Isolation Capacitance

C

ISO

2700

pF

Isolation Resistance

R

ISO

10

MΩ

General Specifications

Parameter

Symbol

Min

Typ

Max

Unit

Calculated Reliability based upon Telcordia SR-
332, Issue 2; Method I Case 3 (I

O

= 80% of I

O, max

,

T

A

=40°C, airflow = 200 lfm, 90% confidence)

MTBF

FIT

2,808,445

356

Hours

10

9

/Hours

Weight

31 (1.1)

g (oz.)