Data Sheet

QBVE060A0S10R4 Barracuda Series; DC-DC Converter Power Modules

45-56Vdc Input; 10.4Vdc, 60.0A, 625W Output

September 9, 2013

©2012 General Electric Company. All rights reserved.

Page 2

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings
only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations
sections of the Data Sheet. Exposure to absolute maximum ratings for extended periods can adversely affect device reliability.

Parameter

Device

Symbol

Min

Max

Unit

Input Voltage*

Continuous

V

IN

-0.3 56

V

dc

Non- operating continuous

V

IN

64

V

dc

Operating Ambient Temperature

All

T

A

-5 85

°C

Short term operating, ≤ 96hrs/year
(See Thermal Considerations section)

-20 90 °C

Storage Temperature

All

T

stg

-40 125

°C

I/O Isolation Voltage (100% factory Hi-Pot tested)

All

750 V

dc

* Input over voltage protection will shutdown the output voltage when the input voltage exceeds threshold level.

Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Operating Input Voltage

V

IN

45 48

56 V

dc

Maximum Input Current

I

IN,max

- - 15

A

dc

(V

IN

=45V, I

O

=I

O, max

)

Input No Load Current

All I

IN,No load

135 mA

(V

IN

= V

IN, nom

, I

O

= 0, module enabled)

Input Stand-by Current

All I

IN,stand-by

20 mA

(V

IN

= V

IN, nom

, module disabled)

External Input Capacitance

All

120

-

600

μF

Inrush Transient

All

I

2

t - - 1

A

2

s

Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 12μH source impedance; V

IN

= 48V, I

O

= I

Omax

; see

Figure 11)

All

-

35

- mA

p-p

Input Terminal Ripple Current

(Measured at module input pin with maximum specified input
capacitance and ൏ 500uH inductance between voltage source

and input capacitance)

5Hz to 20MHz, V

IN

= 45V to 56V, I

O

= I

Omax

All

-

-

800 mA

rms

Input Ripple Rejection (120Hz)

All

-

25

-

dB

CAUTION: This power module is not internally fused. An input line fuse must always be used.

This power module can be used in a wide variety of applications, ranging from simple standalone operation to an integrated part
of sophisticated power architecture. To preserve maximum flexibility, internal fusing is not included, however, to achieve maximum

safety and system protection, always use an input line fuse. The safety agencies require a fast-acting fuse with a maximum rating
of 30A in the ungrounded input lead of the power supply (see Safety Considerations section). Based on the information provided in
this Data Sheet on inrush energy and maximum dc input current, the same type of fuse with a lower rating can be used. Refer to
the fuse manufacturer’s Data Sheet for further information.