GE Industrial Solutions KS24194 Power Wire User Manual

Page 3

Advertising
background image

Data Sheet

KS-24194™ Power Wire

March 2010

Lineage Power

3

Features

Stranded, tin-coated, copper
conductors.

Primary wire insulation is
across-linked ethylene vinyl
acetate (EVA) copolymer
thermosetting material.

Available in a variety of colors.

Wire Classifications and
Ratings

UL Listed 600 V RHH; complies
with UL44 requirements for
building wire for cable tray (1/0
and larger) and raceway
applications in National
Electrical Code-defined dry
and damp locations.

UL Listed per UL1581 vertical
tray flame test (1/0 and larger)
UL Listed as RHH wire per

UL44 at 90 °C with or without
cotton braid.

Listed by UL as Telephone
Central Office Power Cable
rated 105 °C without cotton
braid and 90 °C with cotton
braid under Wires,
Miscellaneous Subject 805.

Listed by UL as Telephone
Central Office Power Cable
rated 60 °C for wet locations
under Wires, Miscellaneous
Subject 805.

UL Listed UL1685, FT4/IEEE

1202 Vertical Tray Fire
Propagation and Smoke
Release Test, which classifies
the wire as LS (Limited Smoke).

RHH is defined in the National
Electrical Code Section 310-13.

Meets Telcordia
GR-347-CORE, Issue 2.

Oxygen index exceeds 28%.

CSA

Certified as Appliance

Wiring Materials (AWM) at 105
°C I B FT4, per CSA Standard
C22.2 No. 210.2 with/without
cotton braid cover.

UL recognized as AWM at 105
°C (without cotton-braid cover)
per UL Subject 758 (style
3578).

Directive 2002/95/EC
compliant (RoHS).

* To obtain a National Electrical Code
RHW rating, an RHH wire would also
require a 75°C wet rating.

† IEEE is a registered trademark of the

Institute of Electrical and Electronics
Engineers, Inc.

‡ CSA is a registered trademark of

Canadian Standards Association.

KS-24194 Power Wire Product Offering

KS-24194 Class I Stranded Conductor Specifications, List 2 and List 4

Product

Stranding

1

Covering

Gauges

Colors

KS-24194 List 2

Class I

(Extra Flexible)

None

8 AWG - 750 kCMil

Blue and Blue Tracer

2,3

, Black, Gray,

Red, and Red Tracer

2,3

KS-24194 List 3

Class B

(Non-Flexible)

Cotton Braid

14 AWG - 750 kCMil

Black

4

, Blue, and Blue Tracer

2,5

,

Green, Gray, Ted, and Red Tracer

2,5

KS-24194 List 4

Class I

Cotton Braid

1/0 AWG - 750 kCMil

Gray, Red

6

, and Blue

6

1. Class I Stranding is per ASTM B-172; Class B Stranding is per ASTM B-8.
2. Tracer power wire has a special marking, similar to lines, running parallel on two sides of the wires.
3. Available in 4/0 AWG and 350 kCMil only.
4. Available in 10 AWG, 8 AWG, 6 AWG, and 2/0 AWG only.
5. Available in 4/0 AWG, 350 kCMil, 500 kCMil, and 750 kCMil.
6. Available in 750 kCMil.

Wire Size

AWG or

kCMil

Area

(CMil)

(Nom.)

Current

Capacity

(Amps)

1

Cond.

Dia.

(in)

Max dc

Resistance

2

Min Bend

Radius

(in)

3

No. of

Strands

Diameter (in)

List 2

List 4

Weight / 100 ft (lb)

List 2

List 4

Max Ship

Length

per Reel

8

16,510

55

0.156

0.6790

1-1/2

41

0.290

82

10,000

6

26,250

75

0.186

0.4360

1-5/8

65

0.320

116

6000

4

41,740

95

0.263

0.2740

2

105

0.405

188

4500

2

66,360

130

0.319

0.1720

2-3/8

161

0.465

279

3000

1/0

105,500

170

0.441

0.1090

3-1/8

266

0.625

0.665

452

479

2000

2/0

133,100

195

0.500

0.0868

3-3/8

342

0.685

0.725

563

593

1500

4/0

211,600

260

0.613

0.0546

4

532

0.800

0.840

835

870

1000

350

350,000

350

0.750

0.0334

4-7/8

855

0.965

1.020

1337

1378

700

500

500,000

430

0.941

0.0234

5-7/8

1221

1.170

1.225

1830

1906

500

750

750,000

535

1.100

0.0157

6-5/8

1850

1.345

1.400

2734

2792

350

1. Ampacities shown here are based on not more than three single, insulated conductors in a raceway with a 30 °C ambient temperature.

(Follow the National Electrical Code Article 310 Type RHH Correction Factors.)

2. In Ohms/1000 ft. at 20 °C.
3. Minimum bend radius is equal to five times the overall wire diameter.

Advertising