Xylem 1580 Series In-Line Mounted Centrifugal Fire Pumps AC2516 User Manual

Series 1580 in-line mounted centrifugal fire pumps, Installation, operation and service instructions, A-c fire pump systems

Advertising
background image

A-C FIRE PUMP SYSTEMS

INSTALLER:

PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Series 1580 In-Line Mounted

Centrifugal Fire Pumps

Installation, Operation and Service Instructions

INSTRUCTION MANUAL

AC2516

DESCRIPTION

The Series 1580 Inline Centrifugal Fire Pump is a close

coupled pump which features – high efficiency, rugged

construction, and in-line mounting. These features make

installation, operation and service easy to perform.

OPERATIONAL LIMITS

Unless special provisions have been made for your pump by

A-C Fire Pump Systems, the operational limits for Series

1580 Pumps are as follows:

MAXIMUM WORKING PRESSURE

Listed on pump nameplate.

SEAL OPERATING LIMITS

PACKING

PH Limitations 7-9; Temperature Range 0 to +200°F

For use on open or closed systems which require a large

amount of makeup water, as well as systems which are

subjected to widely varying chemical conditions and solids

buildup.

Advertising