Installation, Operation and Service Instructions

INSTRUCTION MANUAL 310952B

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

NOTE: This product is not intended for use in potable water applications.

WARNING: California Proposition 65 Warning! This product contains chemicals known

to the State of California to cause cancer and birth defects or other reproductive harm.

SAFETY

INSTRUCTION
This safety alert symbol will be used in this manual to
draw attention to safety related instructions. When used,
the safety alert symbol means ATTENTION! BECOME

ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO

FOLLOW THE INSTRUCTIONS MAY RESULT IN A

SAFETY HAZARD.

OPERATIONAL LIMITS

Circuit Sentry

Flo-Setter

Maximum Limitations

Pressure (PSI) Temperature °F

NPT

300

250

DESCRIPTION
Bell & Gossett Circuit Sentry

TM

Flo-Setter Balance &

Commissioning Valves are precision engineered valves
used in heating and cooling systems for the distribution
of flow in various sections of the system. The dynamic
balancing and commissioning valve ensures easy and
reliable balancing of the system, regardless of any
fluctuations in the differential pressure of the system.
The Bell & Gossett Circuit Sentry

Flo-Setter limits the

maximum flow in the system and can be used in both
variable and constant flow systems. The clear scale on the
lockable handle ensures that flow setting is simple and
user friendly while the integral P/T ports allow verification
of pressure.

INSTALLATION INSTRUCTIONS
Circuit Sentry

Flo-Setter Balance & Commissioning

Valves are uni-directional valves and can be installed in
most altitudes; however, they should be installed in a
position to facilitate the ease of balancing the system. Be
sure to install the Circuit Sentry

Flo-Setter with the arrow

pointing in the direction of flow.

CIRCUIT BALANCE VALVES

WITH NPT CONNECTIONS
Apply pipe compound conservatively to male
connecting fittings only.

CAUTION: The use of Teflon impregnated

pipe compound and Teflon tape on

threads provides lubricity. Care should

be taken to prevent over tightening of the valves

which may damage the Circuit Sentry Flo-Setter.

Check connections for leaks.

OPERATION INSTRUCTIONS
HOW TO USE BELL & GOSSETT CIRCUIT SENTRY

FLO-SETTER BALANCE & COMMISSIONING VALVES

FOR PRE-SET FLOW BALANCING
The Circuit Sentry Flo-Setter Balance & Commissioning
Valve is easily set, and the pre-setting is read on the
scale. The flow rate of the valve can be determined from
the flow rate graphs for the valve dimension in question.
See the flow rate graphs of the valve in the FLOW CURVE
BOOK (G10092) or Submittal (A-609.22 or A-611) for
further information about the adjustment setting.
Select the appropriate size Circuit Sentry Flo-Setter
Balance & Commissioning Valve (normally line size) for
the required GPM.
Please note: The scale is for the adjustment of flow. If you
want to close the branch line, use an isolation ball valve
in conjunction with the Circuit Sentry Flo-Setter.
The handle can be locked after adjustment. Remove the
B&G logo cap and tighten with 5mm hexagonal key.

HOW TO USE BELL & GOSSETT CIRCUIT SENTRY FLO-

SETTER TO PROPORTIONAL BALANCE A SYSTEM
The system is easily balanced by adjusting the pump
according to the required differential pressure across the
critical valve.
When the differential pressure is available the system will
automatically be balanced.