Putting the unit into ser vice, Opera tion and maintenance – Bell & Gossett DN0154D HS Vented Condensate Units Series HSTM User Manual

Page 3

Advertising
background image

3

PUTTING THE UNIT INTO SER

VICE

1.

Assure that the unit is piped in accordance with instructions
on page 2.

2. Isolate tank before performing any system leak test. Do not

pressurize the tank as part of the leak test. Failure to do this
can result in serious injury or death.

3. Check floats and alternators for free operation.

4. Check power leads in accordance with wiring diagram

enclosed in control cabinet (when furnished).

5. Install drain plugs.

6. Fill receiver half full of water to prime pump(s) and prevent

possible damage to pump seals. Avoid freezing conditions
after unit receiver has been filled.

7. Check for proper rotation of all three phase motors.

Rotation must be clockwise looking down on the motor as
indicated by directional arrow on pump casting. If pump
runs backwards, interchange two wires (3 phase only).

8. Throttle plug cock in discharge line until pressure at pump

(while pump is discharging) approaches pump rated pres-
sure. Tighten plug nut to secure adjustment.

9. Remove start-up label (below) from panel (if applicable)

after complying with instructions.

10. If possible, observe operation thru several cycles.

W

ARNING: EXPLOSIBLE

Do not pr

essurize receiver. Isolate receiver during leak

test. Do not plug overflow. Do not restrict vent opening to
atmosphere. Open valves slowly. Failure to follow these
instructions could result in serious injury or death.

W

ARNING: HIGH VOLTAGE

Disconnect and lock out power befor

e connecting or

servicing unit. Failure to follow these instructions could
result in serious injury or death.

CAUTION:

DO NOT RUN DRY.
SEAL DAMAGE MAY OCCUR.

Inspect pump seal r

egularly for leaks. Replace as required.

Failure to follow these instructions could result in injury or
property damage.

CAUTION:

DO NOT REVERSE

Reverse operation can cause extensive damage to

pumps. Jog the motor to test for direction of rotation. Failure
to follow these instructions could result in injury or property
damage.

OPERA

TION AND MAINTENANCE

Operators must be familiar with all sections of this manual to

understand the operation of the unit.

Hot water, steam and electricity can be hazardous.

Check motor nameplate for any lubrication requirements.
Pumps require no lubrication.

NOTICE / AUTO REST

ART

Single phase motors will r

estart automatically after thermal

overload protector trips.

Overload thermal relays in starters must be reset manually.

A properly installed unit should function unattended for long
periods of time. Periodic checks to assure proper operations
are highly recommended. Refer to trouble shooting section
when necessary.

A variety of control options are available and are furnished in
accordance with user specifications. Refer to wiring diagrams
(when furnished) to determine control switch settings.

The inlet strainer (when furnished) is intended to protect the
pump and system. Periodic cleaning should be included in the
maintenance schedule. Check frequently in new systems.

GAGE GLASS MAINTENANCE

(Vented Systems)

Clean gage glass as r

equired using commercial glass cleaner.

Dilute muratic acid may be used if required (observe handling
precautions). Never clean gage glass with wire brushes,
scrapers or harsh abrasives. Check exterior only.

Do not reuse gage glass or packing or seals. Immediately
replace glass which is broken, cracked, chipped, scratched or
otherwise damaged. Inspect periodically with a bright concen-
trated light. Anything which glistens and catches the fingernail
or any star-shaped or crescent-shaped mark which glistens is
cause for replacement. Any gage glass which appears cloudy
or roughened and will not respond to cleaning procedures
should be replaced.

When replacing gage glass, use new packings specified for this
use. Install glass with sufficient end clearance for expansion
(keep glass to metal clearance at each end) and tighten nuts
just enough to avoid leakage (do not over tighten).

W

ARNING: EXPLOSIBLE

Do not pr

essurize receiver. Isolate receiver during leak

test. Do not plug overflow. Do not restrict vent opening to
atmosphere. Open valves slowly. Failure to follow these
instructions could result in serious injury or death.

W

ARNING: HIGH VOLTAGE

Disconnect and lock out power befor

e connecting or

servicing unit. Failure to follow these instructions could
result in serious injury or death.

CAUTION:

SUBSEQUENT DAMAGE

A unit showing symptoms of possible pr

oblems

(overflow, noise, leaks, vibrations, continual operation, etc.)
must be corrected immediately. Failure to follow these
instructions may result in full liability for subsequent injury or
property damage.

SAFETY INSTRUCTIONS
SEE COVER OF THIS MANUAL

ELECTRICIAN/INST

ALLER/OPERATOR

REMOVE AND DESTROY THIS T

AG AFTER —

1. ASSURING THAT ALL PUMPS ROTATE CLOCKWISE PER ARROWS CAST ON VOLUTES. (JOG

PUMP MOMENTARILY TO TEST – INTERCHANGE ANY TWO MOTOR POWER WIRES TO
REVERSE 3PH MOTORS.)

2. ASSURING THAT SHIPPING LOCKS HAVE BEEN REMOVED FROM ALL FLOAT SWITCHES.