The following chart shows the maximum outlet steam
pressure that can be obtained from the main valve. The
outlet steam pressure is based on the air pressure from

the pneumatic temperature pilot to an AP-1A or AP-4A
Pneumatic Pressure Pilot. Intermediate pressures can be
interpolated from the chart.

PNT Air Signal

Maximum Steam Pressure from Main Valve

Outlet Pressure

AP-1A Pressure Pilot

AP-4A Pressure Pilot

psig

Bar

psig

Bar

psig

Bar

9

(0.62)

0

(0.00)

0

(0.00)

10

(0.69)

1

(0.07)

4

(0.28)

11

(0.76)

2

(0.14)

8

(0.55)

12

(0.83)

3

(0.21)

12

(0.82)

13

(0.90)

4

(0.28)

16

(1.10)

14

(0.97)

5

(0.35)

20

(1.38)

15

(1.04)

6

(0.41)

14

(1.66)

18

(1.24)

9

(0.62)

36

(2.50)

20

(1.38)

11

(1.76)

44

(3.00)

25

(1.73)

16

(1.10)

64

(4.40)

30

(2.07)

21

(1.45)

84

(5.80)

9