3

5. After installation check all joints for leakage and retighten

where necessary.

OPERATING INSTRUCTIONS
(SHUTOFF VALVES)

The ball type shutoff valves will function as a service valve to

isolate hydronic equipment for repairs. To close the shutoff

valves move the formed handle a quarter of a turn until the

handle is perpendicular to the valve and piping.

To return the shutoff valve to the open position move the

formed handle one quarter of a turn until it is inline with the

valve body and system piping.

OPERATING INSTRUCTIONS
(Y-STRAINERS)

If strainer pressure drop becomes excessive accumulated dirt

should be blown down through the blowdown line (if installed)

to a drain. If a blowdown line is not installed see the service

instructions for removing and cleaning the strainer.

SERVICE INSTRUCTIONS
(SHUTOFF VALVES)

Periodically inspect the shutoff valves for signs of corrosion or

leakage. If stem leakage is observed the brass hex packing nut

should be tightened slightly until leak stops. If tightening the

packing nut does not stop the leak or signs of leakage are

noted elsewhere, the shutoff valve must be replaced.

SERVICE INSTRUCTIONS
(Y-STRAINERS)

If excessive pressure drop is noted across the Y-Strainer the

internal strainer has collected a lot of dirt and needs to be

cleaned. If a blowdown line was not installed or if blowing

down the strainer has not solved the pressure drop problem,

the Y-Strainer must be disassembled for cleaning.
To clean the strainer first isolate the Y-Strainer from the system

or drain the system. Allow the system to cool to 100˚F (38˚C).

Leave drains open while servicing the strainer.

Using the appropriate size wrench remove the brass nut on the

Y portion of the strainer. Grasp and remove the strainer. Clean

the strainer in water to remove collected debris. Replace the

strainer nut gasket with a new one. Reinstall the strainer and

the strainer nut. Pressurize the system and check for strainer

gasket leaks. If noted, slightly tighten nut until leakage stops.
Periodically inspect the Y-Strainer for signs of corrosion or

leakage. If corrosion or leakage is noted the Y-Strainer must be

replaced.

SERVICE INSTRUCTION (HOSE ASSEMBLIES)

Periodically inspect the hose for signs of leakage, corrosion or

deterioration of the rubber hose. If noted immediately replace

the hose assembly.

WARNING:

Twisted hose assemblies may rupture,

spraying hot and/or pressurized water. Use proper

installation methods to prevent twisting. Failure to follow

these instructions could result in serious personal injury,

death and/or property damage.

WARNING:

It is possible, depending on the age or

condition of the shutoff valve stem seal, for some

liquid to escape when closing the valve. Do not have

eyes or face directly above valve. Failure to follow these

instructions could result in serious personal injury.

WARNING:

Check for proper sealing when using as

an isolation valve. If the seal is not sealing properly,

liquid will continue to flow from the drain valves. In this

case, the shutoff valve must be isolated from the system

and replaced. Failure to follow these instructions could

result in serious personal injury, death and/or property

damage.

WARNING:

Corrosion or leakage are indications

that the shutoff valve may be about to cause serious

damage. The shutoff valve must be replaced. Failure to

follow these instructions could result in serious personal

injury, death and/or property damage.

WARNING:

Hot fluids and/or fluids under pressure

are a safety hazard. Do not service the strainer while

it is hot or under pressure. Failure to follow these instruc-

tions could result in serious personal injury, death and/or

property damage.

WARNING:

Corrosion or leakage are indications

that the Y-Strainer may be about to cause serious

damage. The Y-Strainer must be replaced. Failure to fol-

low these instructions could result in serious personal

injury, death and/or property damage.

WARNING:

Corrosion, leakage or deterioration are

indications that the hose assembly may be about to

cause serious damage. The hose assembly must be

replaced. Failure to follow these instructions could result

in serious personal injury, death and/or property damage.