Xylem CPC Multi Drive Setup User Manual

Xylem Pumps

Advertising
background image

Steps for setting up 2 (or more) communicating Aquavar CPC drives:

1

Connect 3 Wires
to terminals 29,
30 & 31 on both
drives

2

On the Keypad of the first
drive Go To:

Menu

Parameters

Group 11

Parameter 1102

(Application macro)

Change to: Multicontrol

4

Now on the 2

nd

Drive,

Exit out to Groups

Go to Group 22

Parameter 2207

(Pump Address)

Change value to 2

3

Repeat step 2 on the 2nd drive

Repeat steps 3 and 4 for (up to 2) additional
drives as needed

These simple instructions are in addition to the
basic wiring and programming used for setting
up individual drives.

For expanded detail of Aquavar CPC setup and
capabilities, refer to IM167, Aquavar CPC Instruction
and Operation manual.

(Recommend 22AWG 3 or 4 wire shielded cable)