1. Turn off water supply to feeder. Make sure by-

pass valve is closed. Drain tank so water level

is below float chamber. Be cautious - drained

water and feeder may be hot.

2. Remove four screws (A) and remove valve

and strainer assemblies. Move volve and

strainer assemblies to a work bench for further

disassembly operations.

3. With a socket attachment screwdriver bit,

unscrew the valve seat and remove it. Once the

valve seat is removed, the valve stem assembly

will slide out freely.

4. Clean the valve assembly housing thoroughly.

5. Insert the new valve stem assembly into the

valve housing.

6. Carefully screw the new valve seat into position

and tighten securely.

7. Clean strainer.
8. Remove the old gasket and clean the gasket

surface on two bolt flange on the strainer and

valve housing.

9. Re-assemble strainer assembly to the valve

assembly using a new gasket and two screws

(B). Tighten screws to secure.

10. Remove the old gasket and clean the gasket

surface on the 4 bolt flange surface on the valve

assembly housing and head casting.

11. Place the new gasket over the “U” shaped fork

mechanism in the head assembly.

12. Position the stem assembly in the vale assembly

by looking through the outlet connection so that

the “U” shaped fork in the head casting aligns

and engages the roller bearing in the center of

the stem in the valve assembly.

Align holes in the valve assembly, gasket, and

head casting. Assemble using four screws (A)

and secure tightly.

13. Reconnect water supply pipes to inlet of strainer

casting and outlet of valve assembly, open

water supply valve and close tank drain valve.

14. Check operation of feeder before placing

system into operation.

Installation of New Valve Steam Assembly

and Valve Seat

McDonnell & Miller No. 25A Make-up Water Feeder

INSTRUCTION MANUAL

I-SA25A-15

REVISION B

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, Illinois 60053

Phone: (847) 966-3700

Fax: (847) 965-8379

www.xyleminc.com/brands/mcdonnellmiller

McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries.
© 2013 Xylem Inc. I-SA25A-15-B March 2013 Part No. 246733

Advertising