Series 150E and 157E

Low Water Cut-Off/Pump Controllers

For Steam Boilers and Other Level Control Applications

Typical Applications:

– Primary or secondary pump controller/

low water fuel cut-off
for steam boilers

– Motorized valve controller

– Low water and high water cut-off

– Dual pump control

– Alarm actuator

A

B

• Before using this product read and understand instructions.

• Save these instructions for future reference.

• All work must be performed by qualified personnel trained in the proper application, instal-

lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.

• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be

0 psi (0 bar) before servicing.

• To prevent electrical shock, turn off the electrical power before making electrical connections.

• This low water cut-off must be installed in series with all other limit and operating controls

installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.

• We recommend that secondary (redundant) low water cut-off controls be installed on all

steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of
steam pressure. At least two controls should be connected in series with the burner control
circuit to provide safety redundancy protection should the boiler experience a low-water
condition. Moreover, at each annual outage, the low water cut-offs should be dismantled,
inspected, cleaned, and checked for proper calibration and performance.

• To prevent serious personal injury from steam blow down, connect a drain pipe to the control

opening to avoid exposure to steam discharge.

• To prevent a fire, do not use this low water cut-off to switch currents over 16A, 1 Hp at

120 VAC or 8A, 1 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.

Failure to follow this warning could cause property damage, personal injury or death.

WARNING

CAUTION

!

WARNING

Series 150E

Series 157E

®

with

MERCURY
FREE
1 HP
Relays

U.S. Pat. No. 6,571,625

McDonnell & Miller

Installation & Maintenance

Instructions

MM-414(B)