The “Send Acknowledge” command returns a simple status response which includes the address of

the sensor. Any measurement data in the sensor’s buffer is not disturbed.

Command

Response

“a!”

“a<cr><lf>”

Where:

a

is the sensor address (“0-9”, “A-Z”, “a-z”, “*”, “?”).

15

SDI-12 Command & Response Protocol

Sensors that are able to continuously monitor the phenomena to be measured, such as a cable

position, do not require a “Start Measurement” command. They can be read directly with the R

commands (R0!...R9!). The R commands work exactly like the D (D0!...D9!) commands. The only

difference is that the R commands do not need to be preceded with an M command.

The H-3301/3311 supports the aR0! continuous measurement command.

Continuous Measurements

example of an “ar0!” command:

Command

Response

“aR0!”

“a+X.XX+NNNN<cr><lf>

Where:

X.XX

= Current position (stage), in user programmable units

NNNN

= Current position (raw counts), in raw position counts

The “Continuous Measurement with CRC” command makes a measurement sequence with a CRC

appended to the data.

The H-3301/3311 supports the aRC0! continuous measurement command.

Continuous Measurements with CRC

example of an “arC0!” command:

Command

Response

“aRC0!” “a+X.XX+NNNNYYY<cr><lf>

Where:

X.XX

= Current position (stage), in user programmable units

NNNN

= Current position (raw counts), in raw position counts

YYY

= CRC (ASCII Characters)