2 technical specifications, Modbus communication modules – Xylem 205546 Modbus Communication Modules for Displays User Manual

Page 5

Advertising
background image

5

2.1.2 Technical Specifications

Specification

Description

Mounting

With 4 screws on transmitter’s I/O board

Protection

IP 20

Dimensions

51 x 82 mm ( H x W)

Connectors

One 5-position plugable screw terminal and one 20-pin bus

connector

Temperature

-20 to +60 °C

Settings

One “Termination” dip switch

LEDs

White LEDs for “5V”, “Rx”, “Tx” and “3V3”

Power consump.

Approx. 0.18 VA

Com. type

RS 485 asynchronous, half duplex

Baud rate

300, 1200, 4800, 9600, 19200, 38400, 57600, 115200

Parity

Even, odd, none

Stop bits

1 , 2

Modbus ID offset

0 - 240

Protocol

Modbus RTU

Table 1. Specifications - Modbus and RS 485 Communication Module

2. Communication Modules

Modbus Communication Modules

Advertising