Timer installation, Aquastat installation – Bell & Gossett P58749C AQS-3/4 Aquastat User Manual

Page 2

Advertising
background image

TIMER INSTALLATION

1. Disconnect the electrical supply to the pump.

2. Remove the screw that holds the steel conduit box cover

to the pump.

3. Remove the conduit box cover. The timer assembly replaces

the conduit box cover.

4. Disconnect the black and white motor leads from the power

supply.

5. Position the plastic base for the timer assembly onto the

steel conduit box with the warning/caution label to the rear
of the pump.

6. Secure the plastic timer base to the conduit box with one

8-32 screw provided.

7. Verify that the electrical rating of the timer matches the

values shown on the nameplate of the circulator.

8. Make the electrical connections according to the wiring

diagram provided. (See Figure 2)

9. Position the cover/timer assembly over the base while

insuring that all wires are inside the box. Note that the
cover/timer assembly can only be assembled in one direc-
tion on the base. Line up the screw holes in the cover with
the screw holes in the base.

10. Fasten the cover to the base using (2) 8-32 screws provided.

AQUASTAT INSTALLATION

1. Follow steps 1 and 2 in the timer installation section.

2. Remove the conduit box cover. If the aquastat is installed

without the timer, the steel cover is reassembled on the
pump after the aquastat installation is complete.

3. Fasten the aquastat clip to the discharge or suction pipe of

the pump.

4. Make the electrical connections according to the wiring

diagram provided. (See Figure 1)

5. Reassemble the conduit box cover to the conduit box while

insuring that all wires are inside the box. Reinstall the 8-32
screw to secure the cover to the conduit box.

WARNING: ELECTRICAL SHOCK HAZARD
Disconnect and lock out the power before making

electrical connections. Failure to follow these instructions
could result in serious personal injury or death.

2

WARNING: ELECTRICAL SHOCK HAZARD
Electrical connections are to be made by a qualified

electrician in accordance with all applicable codes, ordi-
nances and good practices. Failure to follow these instruc-
tions could result in serious personal injury, death and/or
property damage.

WARNING: ELECTRICAL SHOCK HAZARD
Electrical connections are to be made by a qualified

electrician in accordance with all applicable codes, ordi-
nances and good practices. Failure to follow these instruc-
tions could result in serious personal injury, death and/or
property damage.

FIGURE 1

BLACK

WHITE

WHITE

BLACK

BLACK

WHITE

WHITE

BLACK

5 4

3

2

1

L

WHITE

N

L

BLACK

CAPACITOR

TIMER

AQUASTAT

FIGURE 2

CAPACITOR