OPERATIONAL INSTRUCTIONS

SYSTEM PREPARATION

Prior to pump start up, closed heating and cooling systems

should be flushed with clean water and drained. The system

should then be filled with clean water having a PH between 7

and 9.

LUBRICATION

Series 1535C pumps are test run and lubricated at the factory.

Motor bearings for the Series 1535C pumps do not require

greasing.

ROTATION

Pump rotation is clockwise when viewed from the back of the

motor. An arrow is provided to show the rotational direction.

PRIMING AND STARTING

Before starting, the Series 1535C pump must be filled with

water. Manual priming may be necessary if the system does

not fill the pump body automatically. Vent plugs are provided

on the pump body to vent the air.

The pump should be started with the discharge valve closed

and the suction valve fully open. After the pump is at operating

speed, the discharge valve should be opened gradually.
Do not attempt to prime a pump while it is running by letting

water into it through its discharge pipe. This is an unsatisfac-

tory method that could damage the pump or motor or possibly

blow out a fuse.

SERVICE INSTRUCTIONS

GENERAL INSTRUCTIONS

If the pump is to be exposed to freezing temperatures, drain

all fluids from the pump.

PERIODIC INSPECTION

Inspect the pump regularly for leaking seals, worn gaskets,

and loose or damaged components. Replace or repair as

required.

REPLACING THE SEAL

The electrical supply must be disconnected and locked out of

service. Loosen the conduit box cover screws and remove the

cover. Disconnect conduit and wiring.

Close the valves on the suction and discharge sides of the

pump (if no valves have been installed, it will be necessary to

drain the system).

Loosen the volute capscrews but do not remove them. Shift

the pump position slightly to allow any pressurized water to

escape.

Remove the volute capscrews and remove the pump assem-

bly from the pump volute.

3

CAUTION: Seal Damage Hazard

Do not run the pump dry – seal damage may occur.

Failure to follow these instructions could result in moderate

personal injury and/or property damage.

WARNING: Hot Water Leakage Hazard

Pressurize the pump body slowly while checking for

leaks at all joints with gaskets.

Failure to follow these instructions could result in serious

personal injury and/or property damage.

WARNING: Electrical Shock Hazard

Disconnect and lockout the power before servicing.

Failure to follow these instructions could result in serious

personal injury or death.

WARNING: Unexpected Start-Up Hazard

Disconnect and lockout power before servicing.

Failure to follow these instructions could result in serious

personal injury, death and/or property damage.

CAUTION: Extreme Temperature Hazard

Allow the pump temperature to reach an acceptable

level before proceeding. Open the drain valve and do not

proceed until the liquid has completely drained. If the liquid

does not stop flowing from the drain valve, then the isola-

tion valves are not sealing and should be repaired before

continuing. After the liquid has stopped flowing, leave the

drain valve open and continue. Remove the drain plug

located on the bottom of the pump volute. Do not reinstall

this plug or close the drain valve until the reassembly is

complete.

Failure to follow these instructions could result in moderate

personal injury and/or property damage.

WARNING: Excessive Pressure Hazard

Make certain that the internal pressure is relieved

before continuing.

Failure to follow these instructions could result in serious

personal injury and/or property damage.