Commissioning, Startup, Operation,

and Shutdown

Preparation for startup

WARNING:
Explosion hazard. Do not short battery terminals together or damage the battery.

WARNING:
• Failure to follow these precautions before you start the unit will lead to serious personal

injury and equipment failure.

• Do not operate the pump below the minimum rated flows or with the suction or

discharge valves closed. These conditions can create an explosive hazard due to
vaporization of pumped fluid and can quickly lead to pump failure and physical injury.

• If the pump, motor, or piping operate at extremely high or low temperatures, then

guarding or insulation is required. Failure to follow these instructions can result in
serious personal injury or death, and property damage.

• Always disconnect and lock out power to the driver before you perform any installation

or maintenance tasks. Failure to disconnect and lock out driver power will result in
serious physical injury.

• Operating the pump in reverse rotation can result in the contact of metal parts, heat

generation, and breach of containment.

NOTICE:

• Verify the driver settings before you start any pump.
• Make sure that the warm-up rate does not exceed 2.5°F (1.4°C) per minute.

You must follow these precautions before you start the pump:

• Flush and clear the system thoroughly to remove dirt or debris in the pipe system in

order to prevent premature failure at initial startup.

• Bring variable-speed drivers to the rated speed as quickly as possible.
• If temperatures of the pumped fluid will exceed 200°F (93°C), then warm up the pump

prior to operation. Circulate a small amount of fluid through the pump until the casing
temperature is within 100°F (38°C) of the fluid temperature.

At initial startup, do not adjust the variable-speed drivers or check for speed governor or
over-speed trip settings while the variable-speed driver is coupled to the pump. If the
settings have not been verified, then uncouple the unit and refer to instructions supplied
by the driver manufacturer.

Commissioning, Startup, Operation, and Shutdown

Series 60 Installation, Operation, and Maintenance Manual

17