Tempera ture sensor chart – Bell & Gossett P86273B Temperature Sensor for VS Control User Manual

Page 2

Advertising
background image

INSTALLING SENSOR

Strap the cylindrical sensor to the pipe as shown in Fig. 1.

• Wrap the pipe and sensor assembly with insulating tape to

insure adequate heat transfer to the sensor.

• See the wiring instruction sections of the NRF-VS or VS

Control instruction manuals for specific wiring instructions

to the controller. Do not exceed the water temperature

values listed in the temperature sensor chart.

INSULATING TAPE

TEMPERATURE

SENSOR

PIPE

FIG. 1

TEMPERATURE

Value

(in Degrees ºF)

(in 0hms)

30

17264

35

14985

40

13040

45

11374

50

9944

55

8714

60

7653

70

5941

80

4649

90

3667

100

2914

110

2332

120

1879

130

1524

140

1243

150

1021

160

842

170

699

180

583

190

489

200

412

210

349

220

297

230

253

TEMPERA

TURE

SENSOR CHART

WARNING:

Do not apply power to the sensor wires.

Failure to follow these instructions could result in

serious personal injury, death and/or property damage.

Xylem Inc.

8200 N. Austin Avenue

Morton Grove, Illinois 60053

Phone: (847) 966-3700

Fax: (847) 965-8379

www.xyleminc.com/brands/bellgossett

Bell & Gossett is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. P86273B May 2012

Advertising