Should the Flow Limiting Valve require cleaning or

changing the flow rate, follow the instructions below:

1.

Loosen and remove the cap from the valve body.

2.

Pull the cartridge assembly from the valve body

for cleaning or flow adjustment.

3.

Check the cartridge by pushing the orifice washer

into the cartridge housing several times to make

sure spring is functional and to dislodge any

possible debris. Rinse with water if necessary.

4.

Once clean, return flow cartridge to valve

following installation instructions above.

5.

Replace with a new flow cartridge (V58564) if

necessary.

INSULATION

Bell & Gossett recommends that insulation be attached

to the Low Flow Circuit Sentry Model ACL Flow Limiting

Valve after the system has been balanced.

NOTE: Tape or other acceptable means should be used

to secure the insulation to the Low Flow Circuit Sentry

Model ACL Flow Limiting Valve.