Xylem MM 214E Series 61 Low Water Cut-Off User Manual

Series 61 low water cut-off, Warning, Operation

Advertising
background image

INSTRUCTION MANUAL

• Before using this product read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, instal-

lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.

• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be

0 psi (0 bar) before servicing.

• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls

installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.

• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all

steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of
steam pressure. At least two controls should be connected in series with the burner
control circuit to provide safety redundancy protection should the boiler experience a
low-water condition. Moreover, at each annual outage, the low water cutoffs should be
dismantled, inspected, cleaned, and checked for proper calibration and performance.

• To prevent serious personal injury from steam blow down, connect a drain pipe to the control

opening to avoid exposure to steam discharge.

• To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at

120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.

WARNING

CAUTIO

N

!

WARNING

Series 61
Low Water Cut-Off

CUT-OFF

LEVEL

Model 61

Typical Applications:
- Primary or secondary low water cut-off

for hot water and steam boilers.

- Low water cut-off
- High water cut-off
- Alarm actuator

OPERATION

Maximum Boiler Pressure: 20 psi (1.4 kg/cm

2

)

Electrical Ratings

Motor Switch Rating (Amperes)

Voltage

Full Load

Locked Rotor

Pilot Duty

125 VA at

120 or 240 VAC

NOTE: 11 MV is rated at 24 VA @ 24VAC to 120 VAC

MM-214(C) 9/5/06 9:40 AM Page 2

MM-214E

120 VAC

7.4

44.4

240 VAC

3.7

22.2

Advertising