Xylem MM 308D Changing Flow Rate of Series WF-U Uni-Match Electric Water Feeder User Manual

Series wfe and wf-u uni-match, Changing flow rate of, Electric water feeder

Advertising
background image

INSTRUCTION MANUAL

Changing Flow Rate of

®

Electric Water Feeder

• Before using this product read and understand instructions.

• Save these instructions for future reference.

• All work must be performed by qualified personnel trained in the proper application, instal-

lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.

• To prevent electrical shock, turn off the electrical power before making electrical connections.

• To prevent serious burns, bleed off all pressure and let the boiler cool to 80˚F (27˚C) before

opening any pipe.

Failure to follow this warning could cause property damage, personal injury or death.

WARNING

CAUTION

!

WARNING

FEED

INDICATOR

MANUAL

FEED

UNIV

ERSA

L WA

TERF

EEDE

R

WF-U-24

Chic

ago

, IL U

.S.A

.

OPERATION
Maximum water supply pressure 150 psi
Maximum boiler pressure 15 psi
Maximum water temperature 175˚F
Maximum ambient temperature 100˚F

Boiler Size Rating

Recommended Flow

BTUH

Orifice Size GPM

Up to 250,000 BTUH

1

(Up to 1000 sq. ft. EDR)

250,000 to 500,000 BTUH

2

1000 to 2000 sq. ft. EDR

(factory installed)

500,000 to 1,000,000 BTUH

4

2000 to 4000 sq. ft. EDR

MM-308D

Series WFE and WF-U Uni-Match