Xylem MM 624D Paddle Installation Procedure for FS4 3 FS8 W & FS8 WG SL Flow Switches User Manual
Attaching the paddles to flow switch
Revised Paddle
Installation Procedure
For FS4-3, FS8-W and
FS8-WG-SL Flow
Switches
Addendum to: MM-600(E)
MM-601(C)
MM-611(A)
MM-620(A)
Attaching the Paddles to Flow Switch
Insert the 8/32 x 5/16” screw through lock washer, new larger
washer and paddle. Attach screw to the paddle arm and tighten
to a torque of approximately 12-16 lb•in (1.36-1.81 N•m).
NOTE: If two paddles are being installed, they must be stacked one
on top of the other with the longer paddle first in line to the flow.
FLOW
INSTRUCTION MANUAL
MM-624D
Xylem Inc.
8200 N. Austin Avenue
Morton Grove, Illinois 60053
Phone: (847) 966-3700
Fax: (847) 965-8379
www.xyleminc.com/brands/mcdonnellmiller
McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries.
© 2012 Xylem Inc. MM-624D August 2012 Part No. 210588