John Wood Direct Vent Models No Longer in Production User Manual

Page 3

Advertising
background image

Figure 2A - Installation Components.

Figure 2B - Installation Options.
Figure 2B shows the location of a pressure relief and/or

expansion tank if a check valve or pressure reducing

valve is in the cold water supply to the house.
Use OPTION 1 or 2 whichever is more convenient. If

pressure relief valve is used, select one with a setting

172 kPa (25 psi) below the valve rating at tank.

Specially For Direct Vent Water Heater:

Make certain to observe the vent location limitations

complying with the CSA B149 Natural Gas and Propane

Installation Code or ANSI Z223.1 National Fuel Gas

Code and/or local codes. There is some important infor-

mation shown in Figure 3.

For a second or more direct vent unit, the distance

between vent terminals must have a minimum of 305mm

(12 in.).

INSPECT SHIPMENT –– There may be hidden damage

caused by transit. Check to be certain all parts of the

venting system, as shown in Figures 3A through 3M, are

present. Inspect the upper and lower air inlet boxes, rear

air tube and all parts of the venting system (see Figure

2A).

CAUTION

If there are any damaged parts, DO NOT install this water

heater. Report any shortage to your distributor and dam-

age to your carrier.

Note: The four fasteners that are required to secure the

vent terminal to the exterior wall are not provided. These

should be screw type (not nails) chosen for the type of

construction and obtained locally.

CAUTION

Cut edges of corrugated (flex) pipe are extremely sharp.

Wear gloves when handling.

- 3 -

152mm

(6 in.)

SEAL TIGHTLY

OPTION 1

OPTION 2

HOT WATER OUTLET

GAS SUPPLY MANUAL

SHUT-OFF VALVE

SEDIMENT TRAP

UNION - GROUND

JOINT TYPE

FLOOR DRAIN

TEMPERATURE & PRESSURE

RELIEF VALVE

COLD WATER INLET

GAS CONTROL

UPPER AIR

INLET BOX

LOWER AIR

INLET BOX

REAR AIR TUBE

DRAIN PAN

EXPANSION TANK

WATER SUPPLY

TO HOME

WATER METER

WITH BACKFLOW

PREVENTER

PRESSURE

RELIEF VALVE

OVERFLOW

WATER SUPPLY

TO METER

FLOOR DRAIN

Figure 3 - Vent Location Limitations

Vent Terminal must be located at

least 305mm (12 in.) from

Windows, Doors, or any other

Opening through which flue

gases could enter the building.

Any Forced Air Inlet

into the building

Vent

Terminal must be located at least 457mm

(18 in.) from any overhang or building corner or other irregularity

.

305mm (12 in.) Min.

above grade. Higher in

Areas of Heavy Snowfall

Within 3m (10 ft.)

915mm

(36 in.)

Min.

305mm

(12 in.)

Min.

Vent terminal must

be located at least

915mm (36 in.)

above any Forced Air

Inlet into the building

within 3m (10 ft.) of

the Vent Terminal

457mm (18 in.)

Min.

Advertising