IV. Alarm Status

The LCSS Universal Controller provides
both Low Load (surge) protection and
Overload protection. These alarm condi-
tions are displayed on the digital display
(11) and in the “Function” group. Each
mode of protection provides two tiers of
alarm indication. The first tier is a Warning.
When the machine is within 5 percent of
either the Low Load set point or the
Overload set point, the corresponding LED,
Low Load (5) or Overload (2), will flash.
The flashing LED is a visual indicator that
the machine is close to the shutdown set
point and precautionary measures should
be taken. A common “Warning” relay (K3)
will also be energized. The form “C” contact
may be used for remote indication of
“Warning” status.

The second tier is a Shutdown. In the
Shutdown state, the corresponding alarm
LED, Low Load (5) or Overload (2), will illu-
minate and the digital display (11) will show
“L Ld” for Low Load or “O Ld” for Overload.
The starter relay (K1) will also de-energize,
shutting down the blower or vacuum pro-
ducer. The common “Shutdown” relay (K2)
will also energize. The form “C” contact
may be used for remote indication of
“Shutdown” status.

To clear any Warning or Shutdown alarm,
the Reset/Enter “R/E” button (8) must be
pressed for 5 seconds or the control panel
“Stop/Reset” button must be pressed. The
start button must then be pressed to restart
the blower or vacuum producer.

Note: The “O Ld” display will flash if the
motor current exceeds the Full Load
Amp (FLA) rating of the motor that is
programmed into the controller at
Spencer.

V. Wiring Diagram

Specifications

Dimensions (H x W x D)

Overall 5

1

/

8

x 6

1

/

8

x 3

Cutout 4

3

/

4

x 5

3

/

4

x (n/a)

Part Number CTB 90007

Digital Display

7 Segment / LED

5

/

8

High

Display Amps / SCFM

Power Supply

120/240 VAC, 1Ø, 50/60 Hz

Inputs

Analog (1)

0-5A Current Transformer

Digital (2)

120 VAC (Enable, Reset)

Outputs

(3) Provided Rated @: 5 A General

Overload Shutdown,

Purpose, 250 VAC;

1

/

6

HP 120 VAC,

Low Load Shutdown,

2A Pilot Duty, 120 VAC

Common Warning Alarm

Nema Ratings

1, 12, 4

Note: N-1, 12 and 4, Indoor Only

Agency Approvals

UL 873

File #E151368, 97ME50259, DD/215K

CUL

CAN/CSA 22.2, No. 24-93

Note: Dotted lines indicate field wiring.