Iv. alarm status, V. wiring diagram, Specifications – Spencer Bearing Temperature Monitor Control User Manual

Page 3

Advertising
background image

The Spencer Turbine Company

600 Day Hill Road Windsor, CT 06095-4706

TEL 800-232-4321

860-688-8361

FAX 860-688-0098

3

IV. Alarm Status

The BTMC has two tiers of fail safe alarm
monitoring (the relay is energized in normal
operation and de-energized on alarm). The
first tier is a Warning. When the bearing
temperature is 3 percent below the Alarm
set point, the corresponding alarm LED,
Inboard (2) or Outboard (5), will flash. The
flashing LED is a visual indicator that the
bearing temperature is close to the shut-
down set point and precautionary measures
should be taken. A common "Warning"
relay (K3) will also be de-energized on
alarm. The form "C" contact may be
used for remote indication of a "Warning"
condition.

The second tier is an Alarm (Shutdown). In
the Alarm state, the alarm LED, Inboard
(2) or Outboard (5), will illuminate in a
steady state when the bearing temperature
exceeds the set point. The corresponding
relay output will then shut down the blower
or vacuum producer (K1 = inboard, K2 =
outboard). The relay output may also be
used for remote indication of shutdown.

To clear any Warning or Alarm, the
Reset/Enter "R/E" button (8) must be
pressed for 5 seconds. If the bearing
temperature still meets or exceeds the
warning or alarm levels, the controller
cannot be reset. The bearing must be
cooled to an acceptable level before the
blower or vacuum producer will be allowed
to start up again.

V. Wiring Diagram

Specifications

Dimensions (H x W x D)

Overall 5

1

/

8

x 6

1

/

8

x 3

Cutout 4

3

/

4

x 5

3

/

4

x (n/a)

Part Number CTB 90009

Digital Display

7 Segment / LED

5

/

8

High

Display Inboard/Outboard Bearing Temperature

Power Supply

120/240 VAC, 1Ø, 50/60 Hz

Inputs

Analog (2)

100

platinum RTD

Digital (1)

120 VAC (Reset)

Outputs

(3) Provided Rated @: 5 A General

Inboard Shutdown,

Purpose, 250 VAC;

1

/

6

HP 120 VAC,

Outboard Shutdown,

2A Pilot Duty, 120 VAC

Common Warning Alarm

Nema Ratings

1, 2, 12, 4, 4X

Note: N-12, 4 and 4X, Indoor Only

Agency Approvals

UL 873

File #E151368, 97ME50259, DD/215K

CUL

CAN/CSA 22.2, No. 24-93

Note: Dotted lines indicate field wiring.