Cla-Val 136-01/636-01 Solenoid Control Valve Quick Manual User Manual

Solenoid control valve, Model installation / operation / maintenance

Advertising
background image

INTRODUCTION
The Cla-Val Model 136-01/636-01 Solenoid Control Valve is an automatic
valve designed to either close drip tight or open fully by means of a three-
way solenoid control. It is a hydraulically operated, solenoid controlled,
diaphragm type globe or angle valve.

INSTALLATION
1. Allow sufficient room around the valve assembly to make adjustments
and for maintenance.

Note: Before the valve is installed, the pipeline should be flushed to
remove all chips, scale and foreign matter.

2. It is recommended that gate or line block valves be installed upstream
and downstream of the Model 136-01/636-01 to facilitate isolating the
valve for maintenance.

3. Place the valve in the line with flow in the direction of flow arrows or by
the inlet nameplate. Check all fittings and hardware for proper makeup
and that no apparent damage is evident. Be sure main valve cover
nuts/bolts are tight. Pressure in some applications can be very high so be
thorough in checking and inspecting for proper installation and makeup.

4. Cla-Val Valves operate with maximum efficiency when mounted in hor-
izontal piping with the cover UP; however, other positions are acceptable.
Due to size and weight of cover and internal components of six inch valves
and larger, installation with the cover up is advisable. This makes period-
ic inspection of internal parts readily accessible.

5

.

Caution must be taken in the installation of this valve to insure that

galvanic and/or electrolytic action does not take place. The proper use
of dielectric fittings and gaskets are required in all systems using dis-
similar metals.

6. Comply with local and national electrical codes when wiring the
Solenoid Control.

OPERATION AND START-UP
1. Prior to pressurizing the valve assembly make sure the necessary
gauges to measure pressure in the system are installed as required by the
system engineer. A Cla-Val Model X101 Valve Position Indicator can be
installed in the center cover port to provide visual indication of the valve
diaphragm assembly position during start-up.

CAUTION: During start-up and test procedures a large volume of water
may be discharged downstream. Check that the downstream venting is
adequate to prevent damage to personnel and equipment. If the main
valve closes too fast it may cause surging in upstream piping.

2. If isolation valves (B) are installed in pilot system open these valves.
(see schematic).

3. The 3-way Solenoid Control (2) applies or relieves pressure in the
main valve cover chamber and provides the following action:

Note: Solenoids are not reversible because of different internal construc-
tion between Energize to open and De-energize to open solenoids.

4. Check that solenoid control (2) is set to close main valve.

Slowly open the gate or block valve at inlet of the main valve.

Solenoid Control Valve

136-01/636-01

MODEL

INSTALLATION / OPERATION / MAINTENANCE

SOLENOID CONTROL (2)

POSITION

ENERGIZED

DE-ENERGIZED

PORT

FLOW

1

TO

2

3

TO

1

E

NERGIZED

T

O

O

PEN

136-01 S

ERIES

MAIN VALVE (1)

OPEN

CLOSED

D

E

-E

NERGIZED

T

O

O

PEN

136-01 S

ERIES

MAIN VALVE (1)

CLOSED

OPEN

5. Carefully loosen tube fittings at highest points and bleed air from sys-
tem. Carefully loosen the plug at top of main valve cover. If X101 Valve
Position Indicator is installed, carefully open the bleed valve at top of
Indicator. Bleed air from cover and tighten plug or bleed valve. Tighten
tube fittings.

6. Slowly open downstream gate or block valve. Check the operation of
the valve by energizing and de-energizing the solenoid. The valve should
open fully and close drip tight. The valve needs minimum 5 psi differen-
tial under flowing codition.

MAINTENANCE
1. Cla-Val Valves and Controls require no lubrication or packing and a
minimum of maintenance. However, a periodic inspection schedule
should be established to determine how the fluid handled is affecting the
efficiency of the valve assembly. Minimum of once per year.
2. Repair and adjustment procedures of the Cla-Val Hytrol main valve
and control components are included in a more detailed IOM manual. It
can be downloaded from our web site (www.cla-val.com) or by contacting
a Cla-Val Regional Sales Office.
3. When ordering parts always refer to the catalog number and stock
number on the valve nameplate.

SYMPTON

PROBABLE CAUSE

REMEDY

Main Valve

Fails to Close

No flow condition

Inspect downstream piping for
closed valve or obstruction

Too low pressure differential
across valve
(Needs minimum 5psi differential
under flow coditions)

Restrict valve opening with
Cla-Val X102A
limiting assembly
(Contact Cla-Val)

Closed isolation valves in pilot
system, or in main line

Open valves

Lack of cover chamber pressure Check upstream

pressure, tubing needle
valves for restriction

Diaphragm damaged

Replac diaphragm

Mechanical obstruction
Object lodged in valve
Worn disc

Remove obstruction

Replace disc

Badly scored seat

Replace seat

CNA needle valve closed

Open this speed control to
allow pressure to cover

Main Valve
Fails to Open

Closed isolation valves in pilot
system, or in main line
Insufficient line pressure
Diaphragm assembly inoperative

Open valves

Clean & polish stem
Replace and defective or
damaged parts

Main Valve
Vibrates when
Closed

Air in cover

Bleed all air from valve