Cla-Val 93-01/693-01 Quick Manual User Manual

Pressure reducing & solenoid shutoff valve, Model installation / operation / maintenance

Advertising
background image

3. The three-way Solenoid Control applies or relieves pressure in the
cover chamber of the Auxiliary Hytrol Valve (4) in the control piping.
The following action takes place:
4. When the Solenoid allows the main valve to open, the CRD
Pressure Reducing Controls (3) is in command of Hytrol Main Valve.
5. Open the upstream gate or block valve just slightly to allow the valve
assembly and control system to fill with liquid.
6. Carefully loosen tube fittings at highest points and bleed air from the
system. Loosen the vent valve at the top of the main valve cover. If an
X-101 Valve Position Indicator is installed, carefully loosen the vent
valve at top of the Indicator. Bleed air from the cover and tighten plug
or bleed screw. Tighten tube fittings.
7. Open fully the upstream gate or block valve carefully.
8. Slowly open the downstream gate or block valve. Flow should occur
and discharge pressure should increase to the set point of the CRD
Control and remain constant.
9. Adjust the CRD Control to desired outlet pressure. To change pres-
sure setting, turn the adjusting screw clockwise to increase pressure,
counter-clockwise to decrease pressure. There should be flow through
valve during outlet pressure adjustments. When the desired setting
has been made, tighten jam nut and replace cover.
10.To check the operation of the valve, open and close the downstream
gate valve. The downstream pressure should remain constant.
11. If opening and closing speed controls (C or S) are installed in the
valve pilot system, fine tune the opening and closing speed of the main
valve while performing step 10. Turn the adjustment stem on the clos-
ing speed control “C” clockwise to make the main valve close slower.
Turn the adjusting stem on the opening speed control “S” clockwise to
make the main valve open slower. When adjustments have been com-
pleted, tighten the jam nuts.
12. To check the operation of the solenoid shutoff feature, alternately
energize and de-energize the solenoid to open and close the main
valve. The main valve should alternately close drip tight and open to
set point of the CRD. The optional manual operator on solenoids over-
rides operation by shifting it to the energized position when small red
knob is fully turned clockwise. By turning small red knob counter-
clockwise fully normal solenoid operation is restored.

MAINTENANCE
1. Cla-Val Valves and Controls require no lubrication or packing and a
minimum of maintenance. However, a periodic inspection schedule
should be established to determine how the fluid handled is affecting
the efficiency of the valve assembly. Minimum of once per year
2. Repair and maintenance procedures of the Cla-Val Hytrol Main
Valve and pilot control components are included in a more detailed
IOM manual. It can be downloaded from our web site (www.cla-
val.com) or obtained by contacting a Cla-Val Regional Sales Office.
3. When ordering parts always refer to the catalog number and stock
number on the valve nameplate.

MODEL

INSTALLATION / OPERATION / MAINTENANCE

93-01/693-01

Pressure Reducing & Solenoid Shutoff Valve

INTRODUCTION
The Cla-Val Model 93-01/693-01 is an automatic valve designed to
reduce a higher inlet pressure to a steady lower downstream pressure
regardless of changing flow rate and/or varying inlet pressure. It is a
hydraulically operated, pilot controlled, diaphragm type globe or angle
valve.
When downstream pressure exceeds the pressure setting of the con-
trol pilot the main valve and pilot valve close drip tight. The control sys-
tem is very sen sitive to slight pressure changes and immediately con-
trols the main valve to maintain the desired downstream pressure.
Pressure setting adjustment is made with a single adjusting screw that
has a protective cap to discourage tampering. A solenoid control is pro-
vided to in tercept the operation of the pressure reducing control to
close or open the main valve.
INSTALLATION
1. Allow sufficient room around the valve assembly to make adjust-
ments and for disassembly.
2. It is recommended that either a gate or block valve be installed
upstream and downstream of the 93-01/693-01 Valve to facilitate iso-
lating the valve for maintenance.
NOTE: BEFORE THE VALVE IS INSTALLED, PIPE LINES SHOULD
BE FLUSHED OF ALL CHIPS, SCALE AND FOREIGN MATTER.
3. Place the valve assembly in the line with flow through the valve in
the direction indicated on the inlet nameplate or by flow arrows. Check
all fittings and hardware for proper makeup and that no apparent dam-
age is evident. Be sure main valve cover nuts/bolts are tight.
Pressure in some applications can be very high so be thorough in
checking and inspecting for proper installation and makeup.
4. Cla-Val Valves operate with maximum efficiency when mounted in hori-
zontal piping with the cover UP; however, other positions are accept-
able. Due to size and weight of cover and internal components of six
inch valves and larger, installation with the cover up is advisable. This
makes periodic inspection of internal parts readily accessible.
5.

Caution must be taken in the installation of this valve to insure

that galvanic and/or electrolytic action does not take place. The
proper use of dielectric fittings and gaskets are required in all sys-
tems using dissimilar metals.

6. Comply with local and national electrical codes when wiring the
Solenoid Control (5).
OPERATION AND START-UP
1. Prior to pressurizing the valve assembly make sure the necessary
gauges to measure pressure in the system are installed as required by
the system engineer. A Cla-Val Model X101Valve Position Indicator may
be installed in the center cover port to provide a visual indication
of the valve stem during start-up.
C A U T I O N : During start-up and test procedures a large volume
of water may be discharged downstream. Check that the downstream
venting is adequate to prevent damage to personnel and equipment. All
adjustments in pressure should be made slowly while under flowing
conditions.
If the main valve closes too fast it may cause surging in
upstream piping.
2. If isolation valves (B) are installed in pilot system, open these valves
(see schematic).

P

OSITION

E

NERGIZED

D

E

-E

NERGIZED

P

ORT

F

LOW

1

TO

2

1

TO

3

E

NERGIZED TO

O

PEN

CLA-VAL 93-01

A

UXILIARY

(4)

AND

M

AIN

V

ALVE

(1)

O

PEN

R

ELIEVES

C

OVER

P

RESSURE

C

LOSED

A

PPLIES

C

OVER

P

RESSURE

D

E

-E

NERGIZED TO

O

PEN

CLA-VAL 93-01

A

UXILIARY

(4)

AND

M

AIN

V

ALVE

(1)

C

LOSED

A

PPLIES

C

OVER

P

RESSURE

O

PEN

R

ELIEVES

C

OVER

P

RESSURE

S

OLENOID

C

ONTROL

(5)

Advertising