Cla-Val 133-11/633-11 User Manual

Metering & flow rate control valve, Model, Schematic diagram

Advertising
background image

133-11

MODEL

(Full Internal Port)

633-11

(Reduced Internal Port)

6

B

B

DPT

H

D2

D3

E

D1

Y

3A

2A

CS2

B

S

C

A

CS2

2B

4

B

3B

DRAIN TO

ATMOSPHERE

9

F

INDEPENDENT
OPERATING
PRESSURE

INLET

OUTLET

5

1

Main Transmission

Line

Isolating Valve

133-11/633-11

Metering & Flow Rate Controller

131VC-1 Electronic

Valve Controller

To Optional Remote

Computer Control (Local)

Computer

Computer

SCADA

To Optional Remote Control

Modem

Modem

DPT

Schematic Diagram

Item Description

1

Hytrol (Main Valve)

2

CS2S Solenoid Control

3

CK2 Solenoid By-Pass

4

131VC-1 Electronic Control

5

X52D-1 Orifice Plate Assembly

6

DPT Differential Pressure Transmitter

Optional Features

Item Description

A

X46A Flow Clean Strainer

B

CK2 (Isolation Valve)

C

CV Flow Control (Closing)

D

Check Valve with Isolation Valve

E

X117D Position Transmitter

F

Independent Operation Pressure

H

Atmospheric Drain

P

X141 Pressure Gauge

S

CV Flow Control (Opening)

Y

X43 "Y" Strainer

Metering & Flow Rate Control Valve

Automatically Maintains Flow Rate

Up to 10:1 Flow Range Control

Ideal For SCADA Systems

Digital or Analog Communications

Retransmission Capabilities

Security System to Prevents Unauthorized Changes

Optional Hydraulic Backup Pilot Control System

The Model 133-11/633-11 Metering and Flow Rate Control Valve accu-
rately meters and maintains flow rate regardless of changing system con-
ditions. It is an electrically operated, electronically directed, hydraulically
actuated diaphragm valve. Included is 131VC-1 Electronic Valve Controller
Microprocessor that responds to differential pressure produced across a
calibrated orifice plate or venturi. Accurate control is assured as very small
changes in the differential produce immediate corrective action in the main
valve. Differential Pressure Transmitter is recallable to suite flow range
requirements.

The Model 133-11/633-11 Metering and Flow Rate Control Valve can also
be configured to perform a wide variety of secondary functions when
combined with hydraulic pilot operation, such as: pressure reducing, pres-
sure sustaining and level control. Any of these functions can be used in
conjunction with electronic control or to provide a separate automatic fail-
safe operation through the use of backup hydraulic pilot systems.

Typical Applications

The 133-11/633-11 is typically installed in
a fluid delivery system where the flow rate
is measured and changed from a remote
location such as a SCADA system

.

Advertising