Cla-Val 61-02KO/661-02KO Trim User Manual

01 ko, Anti-cavitation hytrol valve

Advertising
background image

Anti-Cavitation Hytrol Valve

100-01

KO

Full Open Operation

When pressure in the cover chamber is
relieved to a zone of lower pressure,
the line pressure at the valve inlet
opens the valve, allowing full flow.

Modulating Action

The valve holds any intermediate posi-
tion when operating pressures are
equal above and below the
diaphragm. A Cla-Val “Modulating”
Pilot Control will allow the
valve to automatically com-
pensate for line pressure
changes.

Tight Closing Operation

When pressure from the valve inlet
is applied to the cover chamber, the
valve closes drip-tight.

MODEL

On-Off Control

Modulating

Control

On-Off Control

Principle of Operation

Virtually Cavitation Free Operation

Severe Service Design - High Pressure Differentials

Reduced Noise and Vibration

316 Stainless Steel Disc Guide and Seat Standard

Drip-Tight, Positive Sealing

Service Without Removal From Line

Retrofit to Standard Hytrol Valves

The Cla-Val Model 100-01KO Anti-Cavitation Hytrol Valve is designed for appli-
cations where there is a high potential for damage from cavitation. Specify this
valve series for a wide variety of control valve applications having pressure dif-
ferentials up to 300 psid or for relief valves having atmospheric discharge up to
150 psid.

The 100-01KO Hytrol main valve provides optimum internal pressure control
through a unique anti-cavitation trim design. Constructed of 316 Stainless Steel,
the seat and disc guide trim components feature dual interlocked sleeves con-
taining radial slots that deflect internal flow to impinge upon itself in the center of
the flow path, harmlessly dissipating the potential cavitation damage. This
unique design also lessens the possibility of fouling if large particles in the water
are present due to the large flow path of the radial slots.

The 100-01KO Hytrol is the basic valve used in Cla-Val Automatic Control Valves
for high differential applications requiring remote control, pressure regulation,
solenoid operation, rate of flow control, or liquid level control.

The Anti-Cavitation Trim components can be retrofitted to existing valves if the
application indicates an appropriate need. Please consult factory for details.

(Full Internal Port)

Advertising